Specifications and Reference Data
July 2016
Reference Manual
00809-0100-4728, Rev MB
100
Specifications and Reference Data
Custom alarm and saturation level
Custom factory configuration of alarm and saturation level is
available with option code C1 for valid values. These values can
also be configured in the field using a Field Communicator.
Turn-on time
Performance within specifications in less than 5.0 seconds after
power is applied, when damping value is set to 0 seconds.
Transient protection
The Rosemount 470 prevents damage from transients induced by
lightning, welding, or heavy electrical equipment. For more
information, refer to the Rosemount 470 Product Data Sheet
(document number 00813-0100-4191).
Configuration
For standard and custom configuration information, see
Standard
NAMUR- NE 43 compliant
Linear
Output:
3.9
I
(1)
20.5
1.
I = Process Variable (current output).
3.8
I
20.5
Fail High:
21.75
I
23
21.5
I
23
Fail Low:
3.5
I
3.75
3.5
I
3.6