7.2.3
Warnings
shows a list of diagnostic messages that may be displayed on the Integral
Display, on the handheld communicator, or in Rosemount Radar Master. Warnings are less
serious than errors and in most cases do not result in Analog Output alarms.
In Rosemount Radar Master, warnings are indicated in the
Diagnostics
window.
Table 7-3: Warning Messages
Message
Description
Action
RAM warning
See Diagnostics (Rosemount Radar Master:
Tools
→
Diagnostics
) for further
information on a warning message.
Also see
View diagnostics in Rosemount Radar Master
FPROM warning
Hreg warning
MWM warning
LCD warning
Modem warning
Analog out warning
Internal temperature warning
Other hardware warning
Measurement warning
Config warning
SW warning
7.2.4
Measurement status
Measurement Status messages that may appear on the Integral Display, on the handheld
communicator, in DeltaV, or in Rosemount Radar Master are shown in
:
Table 7-4: Measurement Status
Message
Description
Action
Full tank
The level measurement is in Full Tank
state. The transmitter waits for the
surface echo to be detected at the top of
the tank.
No action needed.
Empty tank
The level measurement is in Empty Tank
state. The transmitter waits for the
surface echo to be detected at the
bottom of the tank.
No action needed.
Probe missing
Probe is not detected.
Check that the probe is correctly
mounted. Check the connection between
probe and transmitter head.
Seal contaminated
Suspected contamination of the seal has
been detected.
Check if the seal connection with the
probe is contaminated.
Reference Manual
Service and troubleshooting
00809-0100-4530
April 2019
Reference Manual
173