Table I-1: Resource Transducer Block Parameters
(continued)
Parameter
Index number
Description
BLOCK_ERR
06
This parameter reflects the error status associated with the hardware
or software components associated with a block. It is a bit string, so
that multiple errors may be shown.
CLR_FSTATE
30
Writing a Clear to this parameter will clear the device FAIL_SAFE if the
field condition has cleared.
CONFIRM_TIME
33
The time the resource will wait for confirmation of receipt of a report
before trying again. Retry will not happen when CONFIRM_TIME=0.
CYCLE_SEL
20
Used to select the block execution method for this resource. The
Rosemount 5300 supports the following:
Scheduled: Blocks are only executed based on the function block
schedule.
Block Execution: A block may be executed by linking to another blocks
completion.
CYCLE_TYPE
19
Identifies the block execution methods available for this resource.
DD_RESOURCE
09
String identifying the tag of the resource which contains the Device
Description for this resource.
DD_REV
13
Revision of the DD associated with the resource - used by an interface
device to locate the DD file for the resource.
DEFINE_WRITE_LOCK
60
Allows the operator to select how WRITE_LOCK behaves. The initial
value is “lock everything”. If the value is set to “lock only physical
device” then the resource and transducer blocks of the device will be
locked but changes to function blocks will be allowed.
DETAILED_STATUS
55
Indicates the state of the transmitter. See Resource Block detailed
status codes.
DEV_REV
12
Manufacturer revision number associated with the resource - used by
an interface device to locate the DD file for the resource.
DEV_STRING
43
This is used to load new licensing into the device. The value can be
written but will always read back with a value of 0.
DEV_TYPE
11
Manufacturer’s model number associated with the resource - used by
interface devices to locate the DD file for the resource.
DIAG_OPTION
46
Indicates which diagnostics licensing options are enabled.
DISTRIBUTOR
42
Reserved for use as distributor ID. No Foundation enumerations
defined at this time.
DOWNLOAD_MODE
67
Gives access to the boot block code for over-the-wire downloads. 0 =
Uninitialized 1 = Run mode 2 = Download mode
FAULT_STATE
28
Condition set by loss of communication to an output block, fault
promoted to an output block or physical contact. When FAIL_SAFE
condition is set, then output function blocks will perform their
FAIL_SAFE actions.
FAILED_ACTIVE
72
Enumerated list of failure conditions within a device.
FAILED_ALM
73
Alarm indicating a failure within a device which makes the device non-
operational.
Resource Transducer Block
Reference Manual
April 2019
00809-0100-4530
446
Rosemount 5300 Level Transmitter