F.4
Diagnostics device errors
In addition to the BLOCK_ERR and XD_ERROR parameters, more detailed information on
the measurement status can be obtained via DIAGN_DEV_ALERT.
lists the
potential errors and the possible corrective actions for the given values. The corrective
actions are in order of increasing system level compromises. The first step should always
be to reset the gauge and then if the error persists, try the steps in
the first corrective action and then try the second.
Table F-17: Device Errors Diagnostics
Bit Number
Value of DIAGN_DEV_ALERT
Description
Corrective action
0
No alarm active
0
0x00000001
Reserved
1
0x00000002
FF card to gauge comm fault
Replace gauge
2
0x00000004
Level measurement failure
Verify device installation and
configuration
3
0x00000008
Temperature measurement
failure
Check ambient temperature. If
ambient temperature ok
replace the device.
4
0x00000010
Volume measurement failure
Check volume configuration
5
0x00000020
Database Error
Load default database to the
device and reconfigure the
device
6
0x00000040
HW Error
Replace device
7
0x00000080
Microwave Unit Error
Replace device
8
0x00000100
Configuration Error
Load default database to the
device and reconfigure the
device
9
0x00000200
SW Error
Replace device
10
0x00000400
Invalid Strap Table
Check the Strapping Table
configuration
11
0x00000800
Internal Temp Warning
Check ambient temperature at
installation site
12
0x00001000
Database Warning
Check the device configuration
13
0x00002000
HW Warning
Check device installation and
configuration
14
0x00004000
Microwave Unit Warning
Check device installation and
configuration
15
0x00008000
Configuration Warning
Check the device configuration
16
0x00010000
SW Warning
Check device installation and
configuration
Reference Manual
Level Transducer Block
00809-0100-4530
April 2019
Reference Manual