3. Parts of the sensor probes, for type 5300 are non-conducting material covering
meatal surfaces. The area of the non-conducting part exceeds the maximum
permissible areas for Group III according to EN 60079-0.2012 clause 7.4:3.
Therefore, when the probe is used in a potentially explosive atmosphere group III,
EPL Da, appropriate measures must be taken to prevent electrostatic discharge.
4. The Ex ia version of model 5300 FISCO device may be supplied by an “Ex ib” FISCO
power supply, when the power supply is certified with three separate safety current
limiting devices and voltage limitation which meets the requirements for type Ex ia.
5. 1/2” NPT threads need to be sealed for dust and water ingress protection, IP 66, IP
67 or “Ex t”, EPL Da or Db is required.
Ui
Ii
Pi
Ci
Li
FISCO parameters
17.5 V
380 mA
5.32 W
4.95 nF
<1 µH
B.7.4
N1 ATEX Type N
Certificate
Nemko 10ATEX1072X
Standards
EN 60079-0:2012, EN 60079-11:2012, EN 60079-15:2010, EN
60079-31:2014
Markings
II 3G Ex nA ic IIC T4 Gc (-50 °C ≤ Ta ≤ +60 °C /+70 °C)
II 3G Ex ic IIC T4 Gc (-50 °C ≤ Ta ≤ +60 °C /+70 °C)
II 3D Ex tc IIIC T69 °C/T79 °C Dc (-50 °C ≤ Ta ≤ +60 °C /+70 °C)
Special Conditions for Safe Use (X):
1. The transmitter circuits does not withstand 500V AC dielectric strength test
according to EN 60079-11 clause 6.3.13 due to earth connected transient
suppressing devices. Appropriate measures have to be considered by installation.
Ui
Ii
Pi
Ci
Li
Safety parameters HART 42.4 V
23 mA
1 W
7.25 nF
Negligible
Safety parameters
Fieldbus
32 V
21 mA
0.7 W
4.95 nF
Negligible
B.8
International
B.8.1
E7 IECEx Flameproof
Certificate
IECEx NEM 06.0001X
Standards
IEC 60079-0:2011, IEC 60079-1:2014-06, IEC 60079-11:2011; IEC
60079-26:2014, IEC 60079-31:2013
Markings
Ex db ia IIC T4 Ga/Gb (-40 °C ≤ Ta ≤ +60 °C /+70 °C)
Ex ta IIIC T69 °C/T79 °C Da (-40 °C ≤ Ta ≤ +60 °C /+70 °C)
Um=250 VAC, IP66/IP67
Product certifications
Reference Manual
April 2019
00809-0100-4530
364
Rosemount 5300 Level Transmitter