2. Insert the centering piece.
The centering piece is delivered from factory and should be used to prevent the
spacers centering the rod from coming loose.
3. Cut the tube to the desired length.
4. Move the centering piece.
5. Cut the rod inside the tube. Ensure the rod is fixed with the centering piece while
cutting.
Postrequisites
After shortening the probe be sure to update the transmitter configuration to the new
probe length.
Related information
3.5
Centering disc for pipe installations
To prevent the probe from contacting the chamber or pipe wall, centering discs are
available for flexible single, rigid single, and flexible twin lead probes. The disc is attached
to the end of the probe. Discs are made of stainless steel, Alloy C-276, Duplex 2205, or
PTFE.
For the segmented rigid single lead probe, up to five PTFE centering discs can be mounted
along the probe, but keep a minimum distance of two segments between the discs.
Additionally, a disc in SST or PTFE (part number 03300-1655-xxxx) can be attached to the
end of the probe.
Reference Manual
Installation
00809-0100-4308
February 2020
Reference Manual
39
Summary of Contents for Rosemount 3308A
Page 8: ...Contents Reference Manual February 2020 00809 0100 4308 viii Rosemount 3308 Series ...
Page 10: ...Introduction Reference Manual February 2020 00809 0100 4308 10 Rosemount 3308 Series ...
Page 22: ...Transmitter overview Reference Manual February 2020 00809 0100 4308 22 Rosemount 3308 Series ...
Page 74: ...Installation Reference Manual February 2020 00809 0100 4308 74 Rosemount 3308 Series ...
Page 96: ...Configuration Reference Manual February 2020 00809 0100 4308 96 Rosemount 3308 Series ...