The Rosemount
™
3308 Series Transmitter can be configured for level, volume, interface
level, interface distance measurements, and interface thickness.
The Rosemount 3308 Series Transmitter can be pre-configured according to the ordering
specifications in the Configuration Data Sheet.
D.2.1
Guided setup
Basic setup
Tank geometry
The basic transmitter configuration includes setting the tank geometry parameters. For
interface measurements the dielectric constant of the top liquid must also be given. For
some applications with heavy vapor, the Vapor Dielectric Constant must be given as well.
Figure D-2: Tank Geometry
$
&
)
'
(
%
A. Product Level
B. Interface Level
C. Upper Reference Point
D. Probe Length
E. Tank Height
F. Zero Reference Point
Upper Reference Point
The Upper Reference Point is located at the underside of the threaded adapter,
transmitter flange, or Tri-Clamp
®
, as illustrated in
Reference Manual
Configuration parameters
00809-0100-4308
February 2020