Figure 3-2: Free Space Requirement
/
L. Clearance to tank wall
Table 3-1: Recommended Minimum Free Space to Tank Wall or Other Objects in the Tank
Probe type
Condition
Minimum clearance
(L)
Rigid single lead/Segmented rigid single lead
Smooth metal tank wall
4 in. (100 mm)
Disturbing objects such as pipes and beams
Plastic, concrete or rugged metal tank wall
16 in. (400 mm)
Flexible single
Smooth metal tank wall
4 in. (100 mm)
Disturbing objects such as pipes and beams
Plastic, concrete or rugged metal tank wall
16 in. (400 mm)
Coaxial
N/A
0 in. (0 mm)
Flexible twin
N/A
4 in. (100 mm)
(1)
Minimum clearance from tank bottom for the coaxial and rigid single probes is 0.2 in. (5 mm).
Installation
Reference Manual
February 2020
00809-0100-4308
26
Rosemount 3308 Series