Table 6-3: Configuration Error Details (D:)
Message
Description
Recommended actions
Lower Range Value or Upper Range
Value is out of limits
The lower/upper range value is outside
the lower/upper sensor limits. This is
outside the range where the sensor
works properly, hence the
measurement may be unreliable.
•
Check the lower and upper range
values in relation to the sensor
limits.
Configured Measurement Mode not
Supported
The configured Measurement Mode
does not work since support has not
been purchased.
1. Upgrade the device.
2. Change the Measurement Mode
Volume Configuration Error
The volume cannot be calculated
correctly with the current
configuration.
1. Check that the level-volume
values in the strapping table are
entered in increasing order, refer
to
2. Check that the number of
strapping points to use is correct.
3. Check size measures in the
Volume Setup.
Unsupported Probe and Nozzle
Configuration
Rigid Single Lead 0.5 in / 13 mm probe
is configured in combination with 1.5
inch Nozzle. This combination is
invalid and results in unreliable
measurement.
•
Install a nozzle with a supported
inner diameter and re-configure
transmitter.
Parameter Out of Limits
One or more of the configuration
values, in a set that belongs together,
has been changed and reduced the
measurement range of the device.
1. Check the configured values for
Probe Length, Vapor Dielectric
Constant, and Upper Product
Dielectric Constant.
2. Restore default settings and
reconfigure the device.
Low Low Level Alert configuration is
invalid
Low Low Level Alerts will not be raised
as expected because of invalid
configuration.
•
Check entered limit and deadband
values in comparison with entered
tank and probe parameters such as
probe length, tank height etc.
Low Level Alert configuration is invalid Low Level Alerts will not be raised as
expected because of invalid
configuration.
•
Check entered limit and deadband
values in comparison with entered
tank and probe parameters such as
probe length, tank height etc.
High Level Alert configuration is invalid High Level Alerts will not be raised as
expected because of invalid
configuration.
•
Check entered limit and deadband
values in comparison with entered
tank and probe parameters such as
probe length, tank height etc.
High High Level Alert configuration is
invalid
High High Level Alerts will not be
raised as expected because of invalid
configuration.
•
Check entered limit and deadband
values in comparison with entered
tank and probe parameters such as
probe length, tank height etc.
Service and troubleshooting
Reference Manual
February 2020
00809-0100-4308
110
Rosemount 3308 Series
Summary of Contents for Rosemount 3308A
Page 8: ...Contents Reference Manual February 2020 00809 0100 4308 viii Rosemount 3308 Series ...
Page 10: ...Introduction Reference Manual February 2020 00809 0100 4308 10 Rosemount 3308 Series ...
Page 22: ...Transmitter overview Reference Manual February 2020 00809 0100 4308 22 Rosemount 3308 Series ...
Page 74: ...Installation Reference Manual February 2020 00809 0100 4308 74 Rosemount 3308 Series ...
Page 96: ...Configuration Reference Manual February 2020 00809 0100 4308 96 Rosemount 3308 Series ...