
Reference Manual
00809-0100-4716, Rev JA
May 2008
4-17
Rosemount 3095 MultiVariable
FIELDBUS
MAINT_ALARMS
A maintenance alarm indicates the device or some part of the device needs
maintenance soon. If the condition is ignored, the device will eventually fail.
There are five parameters associated with MAINT_ALARMS, they are
described below.
MAINT_ENABLED
The MAINT_ENABLED parameter contains a list of conditions indicating
the device or some part of the device needs maintenance soon.
Below is a list of the conditions with the highest priority first.
1.
Primary Value Degraded
2.
Secondary Value Degraded
3.
Configuration Error
4.
Calibration Error
MAINT_MASK
The MAINT_MASK
parameter will mask any of the failed conditions listed
in MAINT_ENABLED. A bit on means that the condition is masked out
from alarming and will not be reported.
MAINT_PRI
MAINT_PRI
designates the alarming priority of the MAINT_ALM, “Process
Alarms” on page 4-25. The default is 0 and the recommended values is 3
to 7.
MAINT_ACTIVE
The MAINT_ACTIVE
parameter displays which of the alarms is active.
Only the condition with the highest priority will be displayed. This priority is
not the same as the MAINT_PRI parameter described above. This priority
is hard coded within the device and is not user configurable.
MAINT_ALM
An alarm indicating the device needs maintenance soon. If the condition is
ignored, the device will eventually fail.
Summary of Contents for Rosemount 3095
Page 2: ......
Page 8: ......
Page 130: ...Reference Manual 00809 0100 4716 Rev JA May 2008 Rosemount 3095 MultiVariable 5 24 ...