Reference Manual
00809-0100-4716, Rev JA
May 2008
3-15
Rosemount 3095 MultiVariable
HART
c. To restore the selected process variable to its factory default
calibration, select “Factory Trim Recall” and click “Next.”
1. Read the warning message and click “Next.”
2. Select “Yes” to implement the default calibration, and click
“Next.”
3. Read the warning message, and click “Next.”
4. Click “Finish.”
d. To zero the sensor reading for the selected process variable (not
available for Temperature Sensor Calibration), select “Zero
Sensor,” and click “Next.”*
1. Read the warning message and click “Next.”
2. Select “Yes” to zero the current sensor reading, and click “Next.”
3. Read the warning message, and click “Next.”
4. Click “Finish.”
Figure 3-12. Sensor Trim
Options Screen
* NOTE: Do not zero an AP sensor unless an absolute 0 pressure (vacuum)
source is available.