Reference Manual
00809-0100-4716, Rev JA
May 2008
5-13
Rosemount 3095 MultiVariable
Error messages
Table 5-7. EA Error Message
Summary.
Alarm text as displayed in
Diagnostics, Error Info
Additional Corrective Action
(If Needed)
The transmitter and Engineering Assistant are not in communication.
1. Verify that all cables correctly attached.
2. See Table 5-3.
Communications Error: Device is in write protect mode
Move the write protect (security) jumper on
the output board (see Figure 2-4).
Communications Error: Entered analog current value is too low
These messages occur when entering invalid
values. Enter a different value, and retry the
operation.
Communications Error: Number of preambles requested is too high
Communications Error: Number of preambles requested is too low
Communications Error: Requested burst command is invalid
Communications Error: Requested burst mode is invalid
Communications Error: Requested local keys control code is invalid
Communications Error: Sensor slope trim point value is too high
Communications Error: Sensor slope trim point value is too low
Communications Error: Sensor offset trim point value too high
Communications Error: Sensor offset trim point value too low
Communications Error: Excess trim correction was attempted
Communications Error: Trim span from offset to slope values too small
DP (Differential Press) is below Lower Internal Limit
See Table 5-4
DP (Differential Press) is above Upper Internal Limit
SP (Static Press) is below Lower Internal Limit
SP (Static Press) is above Upper Internal Limit
PT (Process Temp) is below Lower Internal Limit
PT (Process Temp) is above Upper Internal Limit
ST (Sensor Temp) is below Lower Internal Limit
ST (Sensor Temp) is above Upper Internal Limit
Static Pressure Sensor is Open
See Table 5-3.
Static Pressure Sensor is Shorted
Process Temp Sensor is Disconnected
Sensor Module is Not Updating
Sensor Module Microprocessor is Not Responding
Sensor Hardware is Incompatible
Sensor Board EEPROM Not Initialized
Sensor Board EEPROM Burn Failure
RAM Failure
Transmitter Self Test Failed
Output Board EEPROM Not Initialized
Output Board EEPROM Burn Failure
Flow Application - AP is above Upper Operating Limit
See Table 5-3.
Flow Application - AP is below Lower Operating Limit
Flow Application - PT is above the Upper Operating Limit
Flow Application - PT is below Lower Operating Limit