Reference Manual
00809-0100-4716, Rev JA
May 2008
4-15
Rosemount 3095 MultiVariable
FIELDBUS
The FEATURE_SEL parameter enables the user to select a hardware or
software write lock or no write lock capability. To enable the hardware security
function, enable the HW_SEL bit in the FEATURE_SEL parameter. When this
bit has been enabled the WRITE_LOCK parameter becomes read only and
will reflect the state of the hardware switch. In order to enable the software
write lock, the SW_SEL bit must be set in the FEATURE_SEL parameter.
Once this bit is set, the WRITE_LOCK parameter may be set to “Locked” or
“Not Locked.” Once the WRITE_LOCK parameter is set to “Locked” by either
the software or the hardware lock, all user requested writes as determined by
the DEFINE_WRITE_LOCK parameter shall be rejected.
The DEFINE_WRITE_LOCK parameter allows the user to configure whether
the write lock functions (both software and hardware) will control writing to all
blocks, or only to the resource and transducer blocks. Internally updated data
such as process variables and diagnostics will not be restricted by the
security switch.
The following table displays all possible configurations of the WRITE_LOCK
parameter.
FEATURES_SEL
FEATURES_SEL is used to turn on any of the supported features. The default
setting of the 3095 does not select any of these features. Choose one of the
supported features if any.
MAX_NOTIFY
The MAX_NOTIFY parameter value is the maximum number of alert reports
that the resource can have sent without getting a confirmation, corresponding
to the amount of buffer space available for alert messages. The number can
be set lower, to control alert flooding, by adjusting the LIM_NOTIFY
parameter value. If LIM_NOTIFY is set to zero, then no alerts are reported.
FEATURE_SEL
HW_SEL bit
FEATURE_SEL
SW_SEL bit
SECURITY SWITCH
WRITE_LOCK
WRITE_LOCK
Read/Write
DEFINE_WRITE_LOCK
Write access
to blocks
0 (off)
0 (off)
NA
1 (unlocked)
Read only
NA
All
0 (off)
1 (on)
NA
1 (unlocked)
Read/Write
NA
All
0 (off)
1 (on)
NA
2 (locked)
Read/Write
Physical
Function
Blocks only
0 (off)
1 (on)
NA
2 (locked)
Read/Write
Everything
None
1 (on)
0 (off)
(1)
0 (unlocked)
1 (unlocked)
Read only
NA
All
1 (on)
0 (off)
1 (locked)
2 (locked)
Read only
Physical
Function
Blocks only
1 (on)
0 (off)
1 (locked)
2 (locked)
Read only
Everything
None
(1) The hardware and software write lock select bits are mutually exclusive and the hardware select has the highest priority. When the HW_SEL bit if set to 1
(on), the SW_SEL bit is automatically set to 0 (off) and is read only.