Reference Manual
00809-0100-4716, Rev JA
May 2008
Rosemount 3095 MultiVariable
3-24
HART
Configuration Properties…
The Configuration Properties screen contains device parameters that are
grouped into tabs located at the top of the window. To access the
Configuration Properties window:
1.
Right-click on the transmitter icon.
2.
Click “Configuration Properties…” from the pop-up menu.
When navigating throughout the Configuration Properties screens, the time
bar at the bottom of the screen lets you switch your view between previous
configurations, the current online configuration, and the saved offline
configuration. The history configuration is read-only.
When making changes to the configuration, click “Apply” or “OK” to implement
and save the configuration to the device.
Basic Setup
The basic setup tab provides access to the essential parameters that should
be defined upon initial configuration (see Figure 3-19). These include:
•
Tag
: unique name entered by the user (8 characters) to identify the
transmitter
•
DP, AP, GP, Temp, Flow, and Flow Total
:
units of measure; all
selectable
•
URV Upper Range Value
(20mA output): entered by user to range the
output
•
LRV Lower Range Value
(4mA output): entered by user to range the
output
•
Date, Descriptor, and Message:
used to further help identify the
transmitter for the user
Figure 3-19. Basic Setup tab
S
TEAM
F
LOW
M
AIN
S
TEAM
L
INE
Summary of Contents for Rosemount 3095