Rosemount 3095 MultiVariable
3-28
HART
Flow Tab
The Flow Tab allows for the configuration of flow damping and units of
measure (see Figure 3-23).
•
Flow USL and Flow LSL
: This is a value calculated by the transmitter.
The calculation is dependent on the DP sensor limit and the flow
configuration file.
•
Flow Units
: From the drop-down menu, select the units of measure for
the flow rate. This parameter is also on the “Basic Setup” tab.
•
Flow Damping
: Not a selectable parameter in the 3095 transmitter. To
dampen the flow measurement, go to the “Process Input” tab and set
the DP damping.
Figure 3-23. Flow Tab
GP, PT, and SP Snsr Tabs
The configuration tabs for the SP, GP, and PT sensors display the high and
low sensor limits. There are no writable parameters for these tabs.
Remote Seal Tab
All parameters found under the Remote Seal tab should show “None,” as the
3095 is not generally used with the Rosemount Diaphragm Seals System.
These fields are selectable by the user in cases where remote diaphragm
seals have been assembled to the transmitter.