Section 6: Troubleshooting
March 2014
Troubleshooting
6.3.2
Diagnostic message: maintenance - fix soon
Table 6-3. Status: maintenance – fix soon
Alert name
LCD
display
screen
LOI screen
Problem
Recommended action
No
Temperature
Updates
NO T
UPDATE
NO TEMP
UPDATE
There are no temperature updates
from the sensor to the electronics
1. Ensure the sensor cable
connection to the electronics is
tight.
2. Replace the pressure transmitter.
Pressure Out
of Limits
PRES
LIMITS
PRES OUT
LIMITS
The pressure is either above or
below the sensor limits
1. Check the transmitter pressure
connection to ensure it is not
plugged or the isolating
diaphragms are not damaged.
2. Replace the pressure transmitter.
Sensor
Temperature
Beyond Limits
TEMP
LIMITS
TEMP OUT
LIMITS
The sensor temperature has
exceeded its safe operating range
1. Check the process and ambient
conditions are within -85 to 194
°F (-65 to 90 °C).
2. Replace the pressure transmitter.
Electronics
Temperature
Beyond Limits
The temperature of the electronics
has exceeded its safe operating
range.
1. Confirm electronics temperature
is within limits of -85 to 194 °F
(-65 to 90 °C).
2. Replace electronics board.
Electronics
Board
Parameter
Error
MEMRY
WARN
(also in
advisory)
MEMORY
WARN
(also in
advisory)
A device parameter does not
match the expected value. The
error does not affect transmitter
operation or analog output.
1. Replace the electronics board.
Configuration
Buttons
Operator Error
STUCK
BUTTON
STUCK
BUTTON
Device is not responding to button
presses.
1. Check configuration buttons are
not stuck.
2. Replace the electronics board.