Reference Manual
00809-0100-4108, Rev BA
Section 2: Configuration
March 2014
Configuration
Re-mapping using a field communicator
Re-mapping using AMS Device Manager
1.
Right click on the device and select
Configure
.
2. Select
Manual Setup
and click on the
HART
tab.
3. Assign Primary, secondary, tertiary, and quaternary variables under
Variable Mapping
.
4. Click
Send
.
5. Carefully read the warning and click
Yes
if it is safe to apply the changes.
Re-mapping using local operator interface
Refer to
Figure 2-13
for instructions to remap the primary variable using a Local Operator
Interface.
Figure 2-13. Re-mapping with local operator interface
From the
HOME
screen, enter the Fast Key sequence
Fast Keys
2, 1, 1, 3
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
EXTENDED MENU
CALIBRAT
DAMPING
TRANSFER FUNCT
SCALED VARIAB
ASSIGN PV
TAG
ALARM SAT VALUES
PASSWORD
SIMULATE
HART REV
BACK TO
MENU
EXIT MENU