9
Reference Manual
00809-0100-4108, Rev BA
Section 2: Configuration
March 2014
Configuration
Table 2-1. Rosemount 2088 device revisions and files
2.4
Configuration basics
The Rosemount 2088 can be configured either before or after installation. Configuring the
transmitter on the bench using either a field communicator, AMS Device Manager, or Local
Operator Interface (LOI) ensures all transmitter components are in working order prior to
installation. Verify that the security switch is set in the unlock position (
) in order to proceed
with configuration. See
Figure 4-2 on page 41
for switch location.
2.4.1
Configuring on the bench
To configure on the bench, required equipment includes a power supply, and a field
communicator, AMS Device Manager, or an LOI (option M4). Wire equipment as shown in
Figure 2-1
below. To ensure successful HART communication, a resistance of at least 250
s
must be present between the transmitter and the power supply, see
“Power supply” on page 45
for details. Connect the field communicator leads to the terminals labeled “COMM” on the
terminal block or 1-5V configuration, wire as shown in
Figure 2-1 on page 10
. The Field
communicator is connected to the terminals labeled VOUT/COMM.
Identify device
Find device driver
Review
instructions
Review
functionality
Software
release date
NAMUR
software
revision
(1)
(1)
(1) NAMUR Software Revision is located on the hardware tag of the device.
HART
software
revision
(2)
(2) HART Software Revision can be read using a HART capable configuration tool.
HART
universal
revision
Device
revision
(3)
(3) Device Driver file names use Device and DD Revision, e.g. 10_01. HART Protocol is designed to enable legacy device driver revisions to continue to communicate with
new HART devices. To access new functionality, the new Device Driver must be downloaded. It is recommended to download new Device Driver files to ensure full
functionality.
Manual
document
number
Changes to
software
January 2013
1.0.0
01
7
10
00809-0100-4108
See footnote
(4)
for list of changes.
(4) HART Revision 5 and 7 Selectable, Local Operator Interface, Scaled Variable, Configurable Alarms, Expanded Engineering Units.
5
9
January 1998
N/A
178
5
3
00809-0100-4690
N/A
Set all transmitter hardware adjustments during commissioning to avoid exposing the
transmitter electronics to the plant environment after installation.