26
Reference Manual
00809-0100-4108, Rev BA
Section 2: Configuration
March 2014
Configuration
the control system may request any of the information that is normally available while the
transmitter is in burst mode. Between each message sent by the transmitter, a short pause
allows the Field Communicator, AMS Device Manager, or a control system to initiate a request.
Choosing burst mode options in HART 5
Message content options:
PV only
Percent of Range
PV, 2V, 3V, 4V
Process Variables
Device Status
Choosing burst mode options in HART 7
Message content options:
PV only
Percent of Range
PV, 2V, 3V, 4V
Process Variables and Status
Process Variables
Device Status
Choosing a HART 7 trigger mode
When in HART 7 mode, the following trigger modes can be selected.
Continuous (same as HART5 burst mode)
Rising
Falling
Windowed
On Change
Note
Consult your host system manufacturer for burst mode requirements.