20
Reference Manual
00809-0100-4108, Rev BA
Section 2: Configuration
March 2014
Configuration
Table 2-4. Rosemount alarm and saturation values
Table 2-5. NAMUR-Compliant alarm and saturation values
Table 2-6. Custom alarm and saturation values
Failure mode alarm and saturation levels can be configured using a field communicator, AMS
Device Manager, and the LOI. The following limitations exist for custom levels:
Low alarm level must be less than the low saturation level
High alarm level must be higher than the high saturation level
Alarm and saturation levels must be separated by at least 0.1 mA
The configuration tool will provide an error message if the configuration rule is violated.
Note
Transmitters set to HART multidrop mode send all saturation and alarm information digitally;
saturation and alarm conditions will not affect the analog output. See also
“Establishing
multidrop communication” on page 27
.
Configuring alarm and saturation levels using a field
communicator
Configuring alarm and saturation levels with AMS Device
Manager
1.
Right click on the device, and select
Configure
.
2. Click
Configure Alarm and Saturation Levels
button.
3. Follow screen prompts to configure Alarm and Saturation Levels.
Level
4–20 mA saturation
4–20 mA alarm
Low
3.90 mA (0.97 V)
3.75 mA (0.95 V)
High
20.80 mA (5.20 V)
21.75 mA (5.40 V)
Level
4–20 mA saturation
4–20 mA alarm
Low
3.80 mA (0.95 V)
3.60 mA (0.90 V)
High
20.50 mA (5.13 V)
22.50 mA (5.63 V)
Level
4–20 mA saturation
4–20 mA alarm
Low
3.70 mA - 3.90 mA
3.60 mA - 3.80 mA
High
20.10 mA - 22.90 mA
20.20 mA - 23.00 mA
From the
HOME
screen, enter the Fast Key sequence
Device Dashboard Fast Keys
2, 2, 2, 5