Appendices CM-2201
28
©2015 Nelson Heat Tracing Systems
www.nelsonheaters.com GA2497 Rev. 2
D.3 Module Reset Group (Write Only)
Modbus
Register
Index
Value
Length
Bytes
Variable Name
Description/Value Range
00092
91
2
Acknowledge All
= Set to 1 to Reset
00093
92
2
Reset Max Temp
= Set to 1 to Reset
00094
93
2
Reset Min Temp
= Set to 1 to Reset
00095
94
2
Reset Max Current
= Set to 1 to Reset
00096
95
2
Reset Max GF
= Set to 1 to Reset
00097
96
2
Reset Max Voltage
= Set to 1 to Reset
00098
97
2
Reset Min Voltage
= Set to 1 to Reset
00099
98
2
Reset Energy
= Set to 1 to Reset
00100
99
2
Reset Cost
= Set to 1 to Reset
00101
100
2
Reset Heater On Time (Hours)
= Set to 1 to Reset
00102
101
2
Reset Heater On Percentage
= Set to 1 to Reset
00103
102
2
Reset Statistics
= Set to 1 to Reset
00104
103
2
Reset Low Temp
= Set to 1 to Reset
00105
104
2
Reset High Temp
= Set to 1 to Reset
00106
105
2
Reset Low Current
= Set to 1 to Reset
00107
106
2
Reset High Current
= Set to 1 to Reset
00108
107
2
Reset GF
= Set to 1 to Reset
00109
108
2
Reset GF Trip
= Set to 1 to Reset
00110
109
2
Reset Low Voltage
= Set to 1 to Reset
00111
110
2
Reset High Voltage
= Set to 1 to Reset
00112
111
2
Reset Auto Test
= Set to 1 to Reset
00113
112
2
Reset Continuity Failure
= Set to 1 to Reset
00114
113
2
Reset SSR Shorted
= Set to 1 to Reset
00115
114
2
Reset RTD-A Open
= Set to 1 to Reset
00116
115
2
Reset RTD-A Shorted
= Set to 1 to Reset
00117
116
2
Reset RTD-B Open
= Set to 1 to Reset
00118
117
2
Reset RTD-B Open
= Set to 1 to Reset
00119
118
2
Reset Self-Check Failure
= Set to 1 to Reset