Programming CM-2201
14
©2015 Nelson Heat Tracing Systems
www.nelsonheaters.com GA2497 Rev. 2
7.4.4 Ground Fault Test
This function will test the ground fault trip function of the
controller to ensure proper operation. When selected, the
controller will generate an artificial ground fault current; if
the ground fault current is sensed as being greater than 30
mA, the test passes. The GF test function will verify actual
ground fault current and heater trip. Status of the test will
be displayed as pass or fail. If this test has been invoked
by the “Now” option and it passes, the user is prompted to
reset the ground fault trip, at which time the load is capa-
ble of being re-energized as required. If this test has been
invoked by the “Autotest” option, and it passes, the load is
allowed to be reenergized as required. If this test has been
invoked by the Autotest cycle, and it fails, an Autotest alarm
is generated, but the load is allowed to be reenergized as
required.
1. Display Mode: Advanced
2. Range: Autotest cycle, Now, Disabled
3. Default: Disabled
7.3.11 Reset Module
This selection resets controller memory parameters to
factory default values. If the controllers memory becomes
corrupt, resetting the module will force the controller to
overwrite each register and may correct any problems that
exist.
1. Display Mode: Advanced
2. Range: yes, no
3. Default: no
7.4 Program - System Test
7.4.1 System Test
This message displays the name of the sub-menu when
entered.
1. Display Mode: Advanced
2. Range: N/A
3. Default: N/A
7.4.2 Alarm Output Test
This function is used for testing and commissioning
purposes allowing the alarm output to be forced On, either
for a short period of time, or continuously. At the end of the
specified time duration, the testing option is automatically
disabled. The alarm test function will not operate if the
alarm configuration is set to “Disabled”; the message
“ALARM DISABLED” will appear.
1. Display Mode: Advanced
2. Range: 1-24 hours, Disabled, Continuously
3. Default: Disabled
7.4.3 Heater Test
This function overrides heater control for maintenance
purposes. For normal operation, set to “Disabled”. If a
period of time is selected, the heater is forced On or Off for
the selected interval. If “continuous” is selected, the heater
is forced On or Off until “Disabled” is selected.
1. Display Mode: Advanced
2. Range: 1-24 hours, Disabled, On Continuously
3. Default: Disabled