CM-2201 Appendices
25
©2015 Nelson Heat Tracing Systems
www.nelsonheaters.com GA2497 Rev. 2
D.1 Module Setup Group (Read/Write) Continued
Modbus
Register
Index
Value
Length
Bytes
Variable Name
Description/Value Range
40024
23
2
Heater Test
= x per 1 Hour (1 to 24)
= 32764 if Set to Disable
=32765 if Set to Continuously
40025
24
2
Reserved
40026
25
16
Heater Name
40043
42
4
Heater Settings
b0:Units
0 = Fahrenheit
1 = Celsius
b1:Enable Heater
0 = No
1 = Yes
b2:Manual Override
0 = Off
1 = On
b3:Control Type
0 = On/Off
1 = Proportional
b4-b6:RTD Operation
000 = Single RTD Mode
001 = Backup
010 = Average
011 = Lowest
100 = Highest
101 = High Temp Cutout
b7:RTD Failure Mode
0 = Off
1 = On
b8:Enable Password
0 = Disable
1 = Enable
b9:Display Mode
0 = Normal
1 = Advanced
b10-b11:Default Display
00 = System Status
01 = Heater Status
10 = Heater Temp
b12-b14:Baud Rate
000 = 1200 bps
001 = 2400 bps
010 = 4800 bps
011 = 9600 bps
100 = 19200 bps
b15-b16:GF Test
00 = Auto Test Cycle
01 = Now
10 = Disable
b17:Heater Type
0 = Fixed Resistance
1 = Self-Regulating