1592022020 iCHILL 100D EVO QRG EN rel. 2.0 23.02.2022
18/40
15
TABLE OF THE OUTPUT STATUS IN ALARM CONDITION
15.1 M
ACHINE ALARMS
Alarm
Code
Alarm
description
Comp.
Heaters
Support
heaters
(air/air
unit)
Evaporator
Pump /
Supply fan
Condenser
Pump
Domestic
hot water
Water
pump
Solar
panel
Water
pump
Condenser
fan
Auxiliary
relay
ACF1
...
AC16
Configuration
alarm
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ACFL
Condenser
flow alarm
OFF
(4)
(8)
(8)
(8)
OFF
(3)
(8)
(8)
(8)
(8)
AEE
Eeprom alarm
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
AEFL
Evaporator
flow alarm
OFF
(4)
OFF
(boiler)
(8)
OFF
(3)
(8)
(8)
(8)
(8)
(8)
AEht
High
inlet
evaporator
water
temperature
OFF
OFF
(boiler)
(8)
(8)
(8)
(8)
(8)
(8)
(8)
AHFL
Domestic hot
water
flow
switch alarm
OFF
(6)
(8)
(8)
(8)
OFF
OFF
(8)
(8)
(8)
ALC1
General alarm
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ALC2
General alarm
type 2
OFF
(9)
OFF
(9)
OFF
(9)
OFF
(9)
OFF
(9)
OFF
(9)
OFF
(9)
OFF
(9)
OFF
(9)
ALSF
Phase
sequence
alarm
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ALti
Low
air
temperature of
the evaporator
inlet (air / air
unit) Alarm
AP1
...
AP6
Probe alarm
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
APE1
...
APE8
I/O Expansion
probe alarm
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
APFL
Solar
panel
flow
switch
alarm
OFF
(6)
(8)
(8)
(8)
(8)
(8)
OFF
(8)
(8)
APr1
APr2
Remote
keyboard
probe alarm
OFF
(3)
OFF
(3)
OFF
(3)
OFF
(3)
OFF
(3)
OFF
(3)
OFF
(3)
OFF
(3)
OFF
(3)