1592022020 iCHILL 100D EVO QRG EN rel. 2.0 23.02.2022
12/40
Pushing
once
during
the
programming
To exit from a group of parameters
7.1
KEY
COMBINANTION
KEY
ACTION
FUNCTION
+
Push for 3 seconds together
Enter the programming parameters
Only in Pr3 level: push SET and
DOWN key
Select the parameter level visibility Pr1 / Pr2 / Pr3
+
Push once together
Exit the programming parameters
Push 5 seconds in heat pump
mode
Manual defrost
+
Only in Pr3 programming level:
push SET and then the MENU key
In Pr3 defines if the parameter can be modified or
not in the other levels.
8
FIRST INSTALLING
8.1
ON
BOARD
CLOCK
(OPTIONAL)
In case of power failure the time and date are maintained for about 3 days (at room temperature 25 °C); the
display shows the message "rtC" and it is necessary to set the clock.
8.2
RTC
SETUP
1.
Push
Menu
key continuously for 3 seconds until the bottom display shows
“Hour
” and the top display
shows its value.
2.
Push
SET
one time: the value is blinking.
3.
Use the Up and Down keys to adjust it. Push
SET
one time to confirm.
4.
Push up or down keys and repeat the operations 2. 3. and 4. for all the RTC parameters:
-
Min:
minutes
(0÷60)
-
UdAy:
day of the week
(Sun
= Sunday,
Mon
=Monday,
tuE
=Tuesday,
UEd
= Wednesday,
tHu
=
Thursday,
Fri
=Friday,
SAt
=Saturday)
-
dAy:
day of the month (0÷31)
-
MntH:
month (1÷12)
-
yEAr: