1592022020 iCHILL 100D EVO QRG EN rel. 2.0 23.02.2022
15/40
10.
Push
SET
to confirm the new value
11.
If necessary, modify others parameter
12.
Push
SET
+
UP
keys together to exit parameters programming
11
MENU ( MENU KEY)
Enter the menu:
• press
the menu button;
• press
the UP or DOWN button to select the submenu;
• press
the SET to enter the submenu.
Exit menu functions:
• Press the
menu button or wait the time-out.
Entering the menu, it is possbile to:
•
ALrM
Read and reset the alarms
•
ALOG
Read and reset the alarm log
•
UPL
Upload the parameter into the Hot Key
•
CrEn
Enable
–
disable one or the two circuits
•
COEn
Enable
–
disable one of the compressors
•
Hour
Read and reset the number of compressor running hour
•
COSn
Read and reset the number of compressor starts-up
•
COdt
Read the compressor discharge temperature
•
Cond
Read the condensing fan speed percentage of the proportional output
•
Pout
Read the percentage of the proportional output 0 ÷ 10 Vdc
•
PoEn
Enable
–
disable evaporator or condenser water pumps
•
dF
Time counting to next defrost cycle, under heat pump mode,
•
uS
Read the probe temperatures that enabled to control the auxiliary output
•
SoL
Read temperature, Set point and output status of solar panel
•
FC
Read temperature, Set point and output status of Free cooling
•
trEM
Read probe temperature of the remote panels
•
Et1
Read temperature, pressure, set point of the electronic expansion valve 1
•
Et2
Read temperature, pressure, set point of the electronic expansion valve 2
•
REC
Enable / disable recovery function
11.1
ALARM
LIST:
READ
AND
RESET
ALrM FUNCTION
1.
Push MENU key
2.
The display shows AlrM label
3.
Push
SET
key (Nothing happens if there are not alarms)
4.
The bottom display shows the alarm code and the top display shows the label
rSt,
if it is possible to reset
the alarm, or
NO
if it is not possible to reset the alarm
5.
Push
UP
or
DOWN
to scroll the alarm list (if more than one alarm is active)
6.
Repeat the reset procedure for each alarm