2.2.6.5
2.2.6.5
2.2.6.5
2.2.6.5
Event Management
This menu item permits changing how the Liebert NXL handles Alarms, Faults and Status
information. Each event can be configured for the following:
• Latch (yes/no)—Event stays active in the event window, even if the fault condition has
been cleared, until user acknowledges it by pressing the “Reset” button.
• Audible (yes/no)—Will set Audible alarm when event occurs
• Event log (yes/no)—Will display event in Event log when it occurs
NOTE
You must press “Save” for changes to take effect.
See
Table 6
for a list of alarms, fault and status messages.
Figure 15 Typical Event Management Parameters