Operation and Maintenance Manual
250-300-400-800kVA
Page 70
5 APPENDIX A-UPS ALARM AND STATUS MESSAGES
Table 6 shows alarm and status messages as they appear in Liebert NXL’s touch-screen
and in the history log, along with a description and recommended actions, if any.
If the recommended action fails to correct the condition, contact your factory-authorized
service provider.
The “Service Telephone Number” can be found by pressing “CONFIG,” “Ratings,” “More>>”
on the menu bar.
Event Message
Event Definition
Recommended Action
Auto Restart
Fail
An Automatic Restart was enabled but
has failed to complete. With Automatic
Restart enabled, the unit automatically
restarts after an End of Discharge
(EOD) event. This alarm means that
one of the auto restart requirements
was true, but failed before the restart
sequence completed. For example, one
conditional requirement for Automatic
Restart to occur is that the Rectifier
Input Voltage must be within acceptable
limits. If, during the restart sequence,
the input voltage drops out of tolerance,
the Automatic Restart will fail. This
alarm is self-clearing. When the
condition is no longer present, the alarm
and any control activity tied to the
alarm reverts to normal.
Press “SILENCE” to silence the audible
alarm. Check the active events to
determine the status of the UPS. If “Auto
Restart Fail” is the only alarm present,
attempt a manual start of the unit by
pressing “Startup,” “Manual Start,” then
following the prompts to attempt to place
the unit back online.
If the manual start fails, or if there are
other alarms present that won’t clear,
contact your factory-authorized service
provider.
Auto Rexfer
Failed
The condition that caused an automatic
transfer to bypass failed to clear within
a specified time delay. An example of a
recoverable transfer (one which the
controls may attempt to recover from
automatically) is an overload that
exceeded the overload time curve.
Press “SILENCE” to silence the audible
alarm. Press “RESET” to attempt to clear
active events This does not clear the
“Auto Retransfer Failed” alarm.. If all
other alarm conditions clear, attempt a
manual transfer back to Inverter by
pressing “Transfer,” “UPS.”
If the transfer is successful, press
“RESET” to clear this alarm from the
Active Event Window. If the UPS fails to
transfer and the active messages do not
explain the reason, contact your factory-
authorized service provider.
Batt CB “#”
Open
Battery Circuit Breaker “#” is open.
This status message is self-clearing.
When the condition is no longer present,
the message and any control activity
tied to the status event reverts to
normal. (The Liebert NXL has eight
battery circuit breakers.)
Press “SILENCE” to silence the audible
alarm. Check the status of Battery
Circuit Breaker “#”. If it is open, the
alarm is normal.
If Battery Circuit Breaker “#” is closed,
contact your factory-authorized service
provider.
Table 6
:
Liebert NXL alarm and status messages