Liebert NXL UPS
Operation and Maintenance Manual
250-300-400-800kVA
Page
39
2.4 Manual Procedures
The Liebert NXL UPS is designed to function while unattended by an operator. Many
important functions are handled automatically by the system control logic, as explained in
2.6 -
Automatic Operations
. Other procedures must be performed manually.
Manual procedures available to the operator include Start-up, Load Transfers and
Shutdowns. These procedures are performed by using the touch screen and some manually
operated isolators and switches.
The touch screen lists all steps required for each manual procedure. This section lists step-
by-step controls to operate and conditions to observe in the following manual procedures:
•
Start-up
—including initial start-up, recovering from input power failure, recovering
from battery shutdown and recovering from shutdowns for emergencies or maintenance.
•
Load Transfers
—including transfers from UPS to bypass and retransfers from bypass
to the UPS system.
•
Maintenance Bypass Load Transfers
—including transferring from internal bypass to
maintenance bypass and transferring from maintenance bypass to internal bypass.
•
Shutdowns
—including module shutdowns for maintenance and emergency shutdowns.
NOTE
The following procedure assumes that the UPS installation inspection and initial start-
up have been performed by Liebert Services. A Liebert-authorized representative must
perform the initial system start-up to ensure proper system operation.
2.4.1
Start-up Procedure
CAUTION
CAUTION
CAUTION
CAUTION
The following procedure provides power to the critical load distribution system.
Verify that the critical load distribution is ready to accept power. Make sure that
personnel and equipment are ready for the critical load distribution system to be
energized.
If your installation includes a Maintenance Bypass, you may already be supplying power to
the critical load equipment through the Maintenance Bypass. If there is no power to the
critical load, apply power through the UPS bypass line per the following procedure.