Network Settings
19
5.4
Web Server
Use the Web Server Menu to configure access to the card
through the Web interface. Consult your network adminis-
trator if needed.
5.4.1 Specify Web Server Settings
Terminal Emulation (Serial or TCP/IP Connection) / Telnet
To change any parameters:
1. Choose
IP Network Settings
from the Main Menu, then
Web Server
.
2. Select an option to change, then use the following guide to make changes.
Web Interface
To access Web Server settings through the Web interface:
• Click on the
Configure
tab, then
Web
in the left panel and finally
Edit
in the right panel. After
making changes, click
Save
.
Table 13
Web server settings
Parameter
Description & Valid Settings
Web Server
Mode
Select the operation mode of the Web server.
•
Disabled
- Web server is disabled
•
HTTP
- Standard Web port, not encrypted
•
HTTPS
- Standard secure Web port, all communication is encrypted
HTTP
Transport
Port
Web Server listening port number.
• For HTTP mode (non-encrypted communications), the default port is 80.
• For HTTPS mode (encrypted communications), the default port is 443.
For HTTPS, you must also install a security certificate for Internet Explorer. Refer to the appro-
priate section for your version of Internet Explorer:
•
5.4.2 - Install Security Certificates - Internet Explorer 6 or earlier
•
5.4.3 - Install Security Certificates - Internet Explorer 7 or later
Password
Protect Site
When enabled, the entire site is password-protected. (If disabled, all pages are accessible
without a password except configure and control functions.)
Configuration/
Control
Enable or disable the use of a Web browser to perform configuration and control operations.
Note: This feature affects configuration and control operations from the Web interface only. If
disabled, these functions may still be available using other system interfaces.
Refresh
Interval
The interval in seconds (10 to 600 seconds) between automatic updates of dynamic Web
pages—parametric data and device status in the right panel.
RECOMMENDATION: Consider whether frequent updates will slow down the system. If many
users will access the device simultaneously, select a larger value to best serve all users.
Recommended values range from 20 to 60 seconds.
Web Server Menu
----------------
1: Web Server Mode
HTTP (Not Secure)
2: HTTP Transport Port
80
3: Password Protect Site 'disabled'
4: Configuration/Control 'enabled'
5: Refresh Rate
30 seconds
<ESC>: Cancel menu level
Please select a key ?>
Web
Edit
Configure tab
Summary of Contents for Liebert IntelliSlot IS-WEB485ADPT