Configuration Overview

10

3.5

Open the Web Interface

To access configuration using the Web interface:
1. Open a Web browser such as Internet Explorer, then enter 

the IP address or hostname of the Web card in the address 

bar—e.g., 

http://192.168.0.125

.

2. Click on the 

Configure

 tab, shown at right. Configuration 

Categories appear in the left panel, organized with folder 

icons.

3. Click on any configuration category, and the Connect To 

box opens.

4. Enter the Administrator username and password (both 

case-sensitive):
a.

User Name

 (default is 

Liebert

)

b.

Password

 (default is 

Liebert

)

5. Click 

OK

.

6. Refer to 

3.1 - Guide to Configuration

 for details on each 

function.

7. After making changes, click the 

Save

 button, then click on 

Reinitialize

 to reboot the Web card and put your changes 

into effect (see 

3.6 - Saving Changes and 

Reinitializing the Web Card

). 

3.6

Saving Changes and Reinitializing the Web Card

Follow the applicable steps for your interface to save configuration changes and reinitialize the Web 

card. Changes will not take effect until these steps are completed.

Terminal Emulation (Serial or TCP/IP Connection) / Telnet

• After each change is made, a reminder appears (shown at right).
• Return to the Main Menu, then choose 

Exit and Save

. A mes-

sage appears and remains until the card is reinitialized, followed 

by a message that the process was successful.

Web Interface

• After making each change, click the 

Save

 button. A reminder 

appears each time you make a change (shown at right).

• Without leaving the Configure tab window (below left), click 

Reinitialize

 in the left panel, then click the 

Reinitialize

 button 

at right to reboot the Web card and put your changes into effect.

• A message window appears, shown above right, and remains until the card is reinitialized.

NOTE

For security, change the default username and 

password (see 

5.7 - Change Username / Password

). 

Configuration

Categories

Configure tab

Connect To

Reinitialize

(to save any changes)

New Settings will take effect

when saved

GO TO MAIN MENU AND DO 'EXIT AND

SAVE' TO SAVE YOUR CHANGES!

Exiting and saving...

Configuration saved successfully

First click

Reinitialize

at left

Then click

Reinitialize

button

Progress message window

Summary of Contents for Liebert IntelliSlot IS-WEB485ADPT

Page 1: ...or Business Critical Continuity Liebert IntelliSlot Web Cards Installation Manual Liebert IntelliSlot Web Card Liebert IntelliSlot Web Card LB Liebert IntelliSlot Web Card LBDS Liebert IntelliSlot Web 485 Card ADPT ...

Page 2: ......

Page 3: ...inal Emulation Interface TCP IP Connection 8 3 4 Open the Telnet Interface 9 3 5 Open the Web Interface 10 3 6 Saving Changes and Reinitializing the Web Card 10 4 0 SYSTEM INFORMATION 11 5 0 NETWORK SETTINGS 12 5 1 Boot IP Settings 13 5 2 Domain Name Server DNS Settings 14 5 3 Management Protocol 15 5 4 Web Server 19 5 5 Telnet Server 24 5 6 Time SNTP Menu 24 5 7 Change Username Password 26 5 8 Re...

Page 4: ...settings 14 Table 11 Management protocol ranges 15 Table 12 SNMP communications menu 17 Table 13 Web server settings 19 Table 14 Time Server parameters 25 Table 15 Factory default passwords 26 Table 16 Username and password guidelines 26 Table 17 Factory default passwords 27 Table 18 Messaging menu guide 28 Table 19 E mail configuration guide 29 Table 20 SMS configuration guide 31 Table 21 E mail ...

Page 5: ...NG Risk of electric shock Can cause equipment damage injury or death Service and maintenance work must be performed only by properly trained and qualified personnel and in accordance with applicable regulations and manufacturers specifications Opening or removing the covers to any equipment may expose personnel to lethal voltages within the unit even when it is apparently not operating and the inp...

Page 6: ...t NX and Liebert Hinet UPS models Liebert IntelliSlot Web Card LBDS Compatible with the Liebert DS Precision Cooling unit and the Liebert XDF Liebert IntelliSlot Web 485 Card ADPT Compatible with Liebert AC Power and Precision Cooling systems not equipped with a Liebert IntelliSlot port Liebert IntelliSlot Web cards support both 10Mbit and 100Mbit communication speeds and either half or full duple...

Page 7: ... Web technologies built into each of the Liebert IntelliSlot Web cards Liebert Nform will centrally manage alarm notifications to provide you with an easy interface to access criti cal system information A downloadable edition is available online at nform liebert com 1 6 Liebert MultiLink Support The Liebert IntelliSlot Web card integrates with Liebert s MultiLink software to provide unattended gr...

Page 8: ...ipped with the card 2 Connect the configuration cable to the DB 9 port on the card and to a COM port on your PC 2 1 2 Prepare the Card for Configuration Use terminal emulation software such as Microsoft HyperTerminal to open a connection to the card with the settings in Table 2 Press the Enter key for the Main Menu above right Select IP Network Settings then Boot IP Settings and follow the instruc...

Page 9: ...ver to enable the Modbus application 6 At the next screen select Server ID the default Server ID is 1 but may be any number up to 255 7 Press Esc to return to the Main Menu 8 Select IP Network Settings then Boot IP Settings and follow the instructions to enter an IP ADDRESS NETMASK and GATEWAY 9 Press Esc to return to the Main Menu 10 Choose Exit and Save to save your changes and reboot the card W...

Page 10: ...are for example HyperTerminal Configuration Serial Cable or TCP IP Telnet Use a command prompt enter telnet and the IP address or hostname Configuration TCP IP Web Use a Web browser for example Microsoft Windows Internet Explorer Configuration Monitoring Control TCP IP NOTE The Terminal Emulation and Telnet interfaces present the same menus and choices Table 5 Guide to configuration details Topic ...

Page 11: ... settings shown in Table 6 5 When the message at right appears in the HyperTerminal window press the Enter key 6 In the Main Menu enter the number that corresponds to your choice Refer to 3 1 Guide to Configuration for details on each function 7 After making changes return to the Main Menu and choose Exit and Save to reboot the Web card and put your changes into effect see 3 6 Saving Changes and R...

Page 12: ... appears in the HyperTerminal window press the Enter key 5 Enter the Administrator username and password both are case sensitive a Login username default is Liebert b Password default is Liebert 6 In the Main Menu enter the number that corresponds to your choice Refer to 3 1 Guide to Configuration for details on each function 7 After making changes return to the Main Menu and choose Exit and Save ...

Page 13: ... case sensitive a Login username default is Liebert b Password default is Liebert 4 In the Main Menu enter the number that corresponds to your choice Refer to 3 1 Guide to Configuration for details on each function 5 After making changes return to the Main Menu and choose Exit and Save to reboot the Web card and put your changes into effect see 3 6 Saving Changes and Reinitializing the Web Card NO...

Page 14: ... the Web card Changes will not take effect until these steps are completed Terminal Emulation Serial or TCP IP Connection Telnet After each change is made a reminder appears shown at right Return to the Main Menu then choose Exit and Save A mes sage appears and remains until the card is reinitialized followed by a message that the process was successful Web Interface After making each change click...

Page 15: ...he right panel After making changes click Save NOTE This information also configures the SNMP parameters sysName sysContact sysDescr and sysLocation available using RFC 1213 MIB II Table 7 System information identifiers Item Description Maximum Length Name A name for the Liebert unit 255 characters Contact A contact person or department responsible for maintenance and operation of the Liebert unit...

Page 16: ... Server DNS Settings page 14 5 3 Management Protocol page 15 5 4 Web Server page 19 5 5 Telnet Server page 24 5 6 Time SNTP Menu page 24 5 7 Change Username Password page 26 5 8 Reset Authentication to Factory Defaults page 27 IP Network Settings Menu 1 Boot IP Settings 2 Domain Name Server DNS Settings 3 Management Protocol 4 Web Server 5 Telnet Server 6 Time SNTP 7 Change Administrator Username ...

Page 17: ...Web card to be a network ready device Static Fixed network addresses and other parameters DHCP Central management using dynamic network addresses BootP Older mechanism for central management of network addresses IP address Network address for the Liebert unit Four numbers 0 255 separated by periods for example 10 0 0 5 Netmask Network mask that divides your network into manageable segments Four nu...

Page 18: ...rver settings Parameter Description Valid Settings DNS Mode Obtain DNS server addresses automatically or use specified addresses Note Automatic assignment option is available only if a DHCP server is used to assign IP information to the Web Card Primary DNS Primary IP address of the name server for network Four numbers 0 255 separated by periods e g 192 168 0 1 Secondary DNS Secondary IP address o...

Page 19: ...Telnet Menus SNMP Agent Enable or disable SNMP for remote management SNMP Communications Set up access privileges configure the Web card to send traps described in the next section SNMP Communications Menu For details on viewing support information see 9 2 Events and Parameters Obtain address automatically Specify address Options for how long card retains resolved addresses Click Edit to change se...

Page 20: ... through the Web interface Click on the Configure tab then Management Protocol in the left panel and finally Edit in the right panel After making changes click Save Click on Edit to enable any options List sets frequency of Heartbeat Traps Management Protocol Configure tab ...

Page 21: ...rmation in that MIB This can be enabled or disabled independently of the Liebert Global Products MIB Traps This option enables the RFC 1628 traps to be sent when an alarm event occurs on the device The parent option must be enabled for this to also be enabled Liebert Global Products MIB Enables the Liebert Global Products MIB Enterprise Specific for querying of information in that MIB This option ...

Page 22: ... Enter No confirmation message will appear Type the Entry Number then press Enter Example d 2 then press Enter NOTE Avoid the following setting it permits access by any host and may pose a security risk IP address 0 0 0 0 Access write Community public To make changes Add a device see example at right to enter all parameters in one line Enter a to add an entry then press Enter Enter the IP address ...

Page 23: ...ficate for Internet Explorer Refer to the appro priate section for your version of Internet Explorer 5 4 2 Install Security Certificates Internet Explorer 6 or earlier 5 4 3 Install Security Certificates Internet Explorer 7 or later Password Protect Site When enabled the entire site is password protected If disabled all pages are accessible without a password except configure and control functions...

Page 24: ...ity certificate Open Internet Explorer and enter https followed by the IP address or hostname of the Web card for example https 192 168 0 125 in the address bar The following message appears Click the View Certificate button This opens the Certificate window In the Certificate window above left click the Certificate Path tab In the Certificate Path tab above right click on Allegro Root CA then on ...

Page 25: ...opens Click Next Click on Automatically select the certificate store based on the type of certificate then click Next The final Wizard window appears with a message that the process is complete Click Finish A confirmation box appears with a message that the import was successful Click OK Install Certificate Automatically select ...

Page 26: ... https 192 168 0 125 in the address bar The following message appears Click on Continue to this website not recommended to open a connection to the Web card Click the Certificate Error box next to the address bar shown above left In the window that pops up shown above right click the View Certificates link This opens the Certificate window In the Certificate window above left click the Certificate...

Page 27: ...opens Click Next Click on Automatically select the certificate store based on the type of certificate then click Next The final Wizard window appears with a message that the process is complete Click Finish A confirmation box appears with a message that the import was successful Click OK Install Certificate Automatically select ...

Page 28: ... settings through the Web interface Click on the Configure tab then Telnet in the left panel and finally Edit in the right panel After making changes click Save 5 6 Time SNTP Menu This permits setting time options how often the Web card synchronizes with the Time Server which Time Server to use for synchronization and which the Time Zone the Web card is operating in Telnet Server Menu 1 Telnet Ser...

Page 29: ...nally Edit in the right panel After making changes click Save Table 14 Time Server parameters Parameter Description Telnet Menus SNTP Time Sync Rate This is how often the card will attempt to synchronize its internal clock with the specified time server Time Server This is the server that will be used for synchronization This can be either an IP address or a hostname provided that the DNS options ...

Page 30: ...e Click on the Configure tab then Users in the left panel and finally Edit in the right panel After making changes click Save Table 15 Factory default passwords Type of User Factory Default Description Administrator Username Liebert Full access to configuration and control functions as well as viewing privileges Password Liebert General User Username User Viewing privileges only no access to confi...

Page 31: ...nection Telnet To reset the usernames and passwords to the factory defaults 1 Choose IP Network Settings from the Main Menu then Reset Authentication to Factory Defaults 2 Enter y to reset the Administrator and General User usernames and passwords to the default settings Table 17 Factory default passwords Type of User Factory Default Description Administrator Username Liebert Full access to config...

Page 32: ...Web Interface To access Messaging settings through the Web interface Click on the Configure tab then Messaging in the left panel and finally Edit in the right panel After making changes click Save Table 18 Messaging menu guide Menu item Refer to E Mail Configuration page 29 SMS Configuration page 30 Customize Messages E Mail and SMS page 32 Messaging Menu 1 Email disabled 2 SMS disabled 3 Email Co...

Page 33: ...ntry or e to edit an entry NOTE To specify multiple recipients of the e mail message in the Web interface use a semicolon to separate addresses in the Email To box 64 characters Email Subject The subject line of the e mail By default this is the event description e g AlarmOnBypass but it may be customized 120 characters Email Customize Message The text of the message sent to e mail recipients Choo...

Page 34: ... Save 6 2 SMS Configuration Setting up event notifications for SMS text messages involves two steps enabling the function then specifying the parameters Email Configure tab Edit SMS Configuration Menu 1 SMS From Uninitialized 2 SMS Message Recipients 3 SMS Subject 4 SMS Customize Message 5 SMTP Server Uninitialized 6 Port 25 7 Test SMS 8 View Test SMS Log File ESC Cancel menu level Please select a...

Page 35: ...m where ____ might be a company name To add an SMS address use the format a 1112223333 abc com Multiple addresses must be added individually Changes may be made by entering d to delete an entry or e to edit an entry NOTE To specify multiple recipients of the SMS message in the Web interface use a semicolon to separate addresses in the SMS To box 64 characters SMS Subject The subject line of the me...

Page 36: ...on Location The location of the Liebert unit 4 0 System Information Description Other information about the Liebert unit 4 0 System Information Web Link Port A clickable link to the Web card through the Web interface 5 1 Boot IP Settings The port number of the SMTP server port 6 1 E Mail Configuration 6 2 SMS Configuration Event Consolidation Enable or disable consolidation of events for e mail SM...

Page 37: ...he items to include in each type of message in the Email and SMS columns After making changes click Save Message Consolidation Time Limit Message Consolidation Time Limit allows adjusting the duration the card will wait for additional events before sending a notification E mail Consolidation event limit allows adjusting the number of events each E mail will contain Customize Message Configure tab ...

Page 38: ... factory default settings 1 Choose Factory Settings from the Main Menu then choose Reset to Factory Defaults 2 Enter y yes at the prompt to confirm your choice To cancel enter n no 3 A message appears until the process is complete Web Interface To restore the factory default settings through the Web interface Click on the Configure tab then Factory Defaults in the left panel and finally Reset to F...

Page 39: ...must change the address of one card see Table 22 For the Liebert IntelliSlot Web card the default address is 1 For two Web cards set the address of the second card to 2 For the Liebert IntelliSlot 485 card the default address is 2 For two 485 cards set the address of the second card to 1 Table 22 Factory default MAC addresses Liebert IntelliSlot Card Part Number Factory Default MAC Address Set Nod...

Page 40: ... name contact location and description of the Liebert unit as defined in 4 0 System Information Device Status current status of the Liebert unit and whether any alarms are active if so the most recent alarm is listed Monitor Categories appear at bottom left organized with folder icons and showing the avail able Monitoring functions Click on a category to view parametric data in the right panel The...

Page 41: ...rm an operation click on a Control Operations category at left then click on the appropri ate button in the right panel The example below shows control operations for two Liebert units Table 23 Control operations parameters functions vary by Liebert unit Command Description Abort Commands Prevent any pending commands from being completed Alarm Silence Alarms Temporarily silence an audible alarm th...

Page 42: ...ered on if no network time synchronization has taken place 2 The event ID This is the index number given to events since the start of the history 3 The event text Text stating the type of event and how the card reacted Event Log Controls Scroll immediately to Page 1 of the history Scroll left one page in the history Scroll right one page in the history Scroll immediately to the last page of the hi...

Page 43: ...he following example Press the Enter key to return to the previous menu Web Interface To view Web card information through the Web interface Click on the Support tab then Summary in the left panel The Web card information appears in the right panel MAC Address 00 00 68 16 82 C1 Network Card Model IntelliSlot Web Card Network Card Part OCWEBCARD Manufacture Date APR 28 2004 Serial Number 416701G105...

Page 44: ...iew a list of supported param eters for the Liebert unit as in the example at right These parameters vary according to the Liebert unit where the card is installed Web Interface To view events and parameters through the Web interface Click on the Support tab then Events or Parameters in the left panel The events or parame ters are listed in the right panel The example below shows a list of Events ...

Page 45: ...d all the instructions prior to attempting a firmware upgrade Table A1 Overview of the upgrade process Step For details see 1 Decide which interface to use to connect to the Liebert IntelliSlot card A 2 Connect to the Card Terminal Emulation Telnet or Web Interface 2 Prepare for the upgrade Make sure you have everything needed to perform the upgrade A 3 1 Requirements to Update the Liebert Intelli...

Page 46: ...r key A 2 2 Open the Terminal Emulation Interface TCP IP Connection To connect to the card using terminal emulation software with an Ethernet connection to the Web card 1 Open a terminal emulation application such as HyperTerminal To do this Click the Start button then Programs Accessories Communications and finally HyperTerminal 2 In the Connection Description window enter a name for the connecti...

Page 47: ...terface To connect to the card using the Web interface 1 Open a Web browser such as Internet Explorer 2 Enter the IP address of the Web card in the address bar e g 192 168 0 125 3 Click on a tab at the top of the window A 3 PREPARING TO UPDATE LIEBERT INTELLISLOT FIRMWARE A 3 1 Requirements to Update the Liebert IntelliSlot Card s Firmware Make sure you have the following before starting the updat...

Page 48: ... left panel The Liebert IntelliSlot card model part number and firmware version appear in the right panel A 3 3 Download the Firmware Upgrade File to the Computer To download the upgrade file 1 Open a Web browser such as Internet Explorer 5 5 or newer 2 Navigate to Liebert s Web site www liebert com downloads 3 Choose the firmware upgrade for your card from the selections on the Web page see A 3 2...

Page 49: ...username and password both case sensitive a User Name default is Liebert b Password default is Liebert 4 Click OK The Web HTTP Firmware Update window opens as shown at right below 5 Click on the Browse button to locate the upgrade file This is the file with the extension bin downloaded in A 3 3 Download the Firmware Upgrade File to the Computer Then click Open to return to the update screen 6 When...

Page 50: ...y settings 6 After making changes press the Escape key twice to return to the Main Menu 7 Choose Exit and Save to save your changes and reboot the card Reconnect to the Card 8 Connect to the Liebert IntelliSlot card again if needed see A 2 3 Open the Telnet Interface or A 2 1 Open the Terminal Emulation Interface Serial Connection 9 Choose Firmware Updates from the Main Menu 10 Choose TFTP Update ...

Page 51: ...sing the TFTP method with a Web interface Open a Connection to the Card 1 Open a connection to the Liebert IntelliSlot card if needed see instructions in A 2 4 Open the Web Interface 2 Click on the Configure tab then TFTP in the left panel 3 Enter the Administrator username and password both are case sensitive a Login username default is Liebert b Password default is Liebert TFTP Update Menu 1 IP ...

Page 52: ...TP application and start TFTP Ensure that all settings are ready to transfer the file including the location of the upgrade file Refer to your TFTP user manual for more details 9 Return to the Web interface 10 When ready to begin the download click the Update Firmware button Table A5 Firmware update settings Web Parameter Description Server The IP address of the TFTP server for example 192 168 0 1...

Page 53: ...see A 3 2 Determine the Liebert IntelliSlot Card Type and Firmware Version A 6 UPDATING THE FIRMWARE XMODEM SERIAL METHOD Follow these steps to update the firmware using the Xmodem serial method This method works through the Web card s serial port employing terminal emulation software such as HyperTerminal NOTE Do not close the Web browser during this process or the update will abort NOTE This met...

Page 54: ... to 115200 6 Choose 115200 bps from the menu shown below left 7 From the HyperTerminal menu click on Call then choose Disconnect this will not close the HyperTerminal connection to the card 8 In the HyperTerminal menu bar click on File then choose Properties 9 Click on the Connect To tab and click the Configure button This opens Port Settings tab in the COM1 Properties window as shown below right ...

Page 55: ...ess Enter to continue 20 Repeat Steps 12 through 15 within the 60 second limit to browse to the second upgrade file and download it to the Liebert IntelliSlot card 21 Wait for the Progress window to close after the second file is downloaded Then repeat Steps 16 through 20 to download the third upgrade file This file is the largest and may take 30 minutes or longer to download NOTE After you begin ...

Page 56: ...shown below right 26 Choose 9600 from the Bits Per Second drop down list and click OK then click OK to close the Properties window 27 In the HyperTerminal menu bar click on Call then choose Call from the drop down menu 28 Press the Enter key 29 Choose Exit and Save from the Main Menu to reboot the card When rebooting is complete the upgrade is finished Check the new firmware version if you wish se...

Page 57: ...Updating the Firmware Xmodem Serial Method A13 Notes ...

Page 58: ...Updating the Firmware Xmodem Serial Method A14 ...

Page 59: ......

Page 60: ...red to are trademarks or registered trademarks of their respective owners Technical Support Service Web Site www liebert com Monitoring 800 222 5877 Liebert monitoring emerson com Outside the US 614 841 6755 Single Phase UPS 800 222 5877 upstech emersonnetworkpower com Outside the US 614 841 6755 Three Phase UPS 800 543 2378 powertech emersonnetworkpower com Environmental Systems 800 543 2778 Outs...

Reviews: