Installation Drawings
Liebert
®
APM
™
74
Figure 57 Outline drawing, Liebert BDC for Liebert APM, 15-45kVA
Figure 58 Outline drawing, Liebert BDC for Liebert APM, 15-90kVA
1. All dimensions are in inches (mm).
2. 24" (610) minimum clearance above unit;
36" (914) front access required for service.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through
removable access plates. Remove, punch
to suit conduit size and replace.
5. Control wiring and power wiring must be run
in separate conduits.
6. Only copper cables are recommended.
7. All wiring is to be in accordance with national
and local electrical codes.
Cable Entry
Area
11.4" x 13.2"
(290 x 335mm)
Cable Entry Area
11.4" x 13.2"
(290 x 335mm)
Cable Entry
Area
6.2" x 13.2"
(57 x 335mm)
Cable Entry Area
6.2" x 13.2"
(57 x 335mm)
6.5"
(164mm)
Outside Panel
6.5"
(164mm)
Outside
Panel
11.5"
(292mm)
Outside
Panel
5.5"
(140mm)
34.6"
(870mm)
23.7"
(602mm)
23.6"
(600mm)
39.5" (1000mm)
78.7"
(200mm)
28.3"
(719mm)
Bracket
Centers
6.4"
(162mm)
Outside Panel
X
Y
24"
(609mm)
FRONT VIEW
RIGHT SIDE VIEW
Center
of Gravity
Leveling
Feet
Z
BOTTOM VIEW
TOP VIEW
Maximum
Door Swing - 120°
UAM06008
Rev. 5
Liebert BDC
with Distribution Type
Dimension, in. (mm)
Weight,*
lb (kg)
X
Y
Z
Without Panelboard
11.8" (300)
39.4"
(1000)
14.9" (379)
525 (239)
With Panelboard
11.8" (300)
39.4"
(1000)
14.9" (379)
625 (284)
* Shipping weight, add 100 lb. (45kg)
UAM06010
Rev. 5
1. All dimensions are in inches (mm).
2. 24" (610) minimum clearance above unit;
36" (914) front access required for service.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through
removable access plates. Remove, punch
to suit conduit size and replace.
5. Control wiring and power wiring must be run
in separate conduits.
6. Only copper cables are recommended.
7. All wiring is to be in accordance with national
and local electrical codes.
Cable Entry
Area
11.4" x 13.2"
(290 x 335mm)
Cable Entry Area
11.4" x 13.2"
(290 x 335mm)
Cable Entry
Area
6.2" x 13.2"
(57 x 335mm)
Cable Entry Area
6.2" x 13.2"
(57 x 335mm)
6.5"
(164mm)
Outside Panel
5.5"
(140mm)
6.5"
(164mm)
Outside
Panel
11.5"
(292mm)
Outside
Panel
34.6"
(870mm)
23.7"
(602mm)
23.6" (600mm)
39.5" (1000mm)
78.7"
(200mm)
28.3"
(719mm)
Bracket
Centers
6.4"
(162mm)
Outside Panel
24"
(609mm)
FRONT VIEW
RIGHT SIDE VIEW
Center
of Gravity
Leveling
Feet
Z
BOTTOM VIEW
TOP VIEW
Maximum
Door Swing - 120°
X
Y
Liebert BDC
with Distribution Type
Dimension, in. (mm)
Weight,* lb (kg)
X
Y
Z
No Distribution
11.8" (300)
39.4" (1000)
14.9" (379)
550 (250)
With 2-225A Subfeed Breakers
11.8" (300)
39.4" (1000)
14.9" (379)
660 (300)
With 400A Panelboard
11.8" (300)
39.4" (1000)
14.9" (379)
660 (300)
* Shipping weight, add 100 lb. (45kg)