Installation Drawings
63
Liebert
®
APM
™
Figure 49 UPS dimensions continued, center of gravity—side, top and bottom views
1. All dimensions are in inches (mm).
2. 24" (610) minimum clearance above unit and 12" (305)
rear clearance required for air exhaust and 36" (914)
front access required for service.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through removable
access plates. Remove, punch to suit conduit size and replace.
5. Unit bottom is structurally adequate for forklift handling.
6. Control wiring and power wiring must be run in separate
conduits.
7. Only copper cables are recommended.
UAM2010A
Rev. 2
Detail A
Mechanical
Stop
Caster
39-1/2"
(1000mm)
78.7"
(2000mm)
1.56"
(40mm)
3"
(77mm)
23.4"
(595mm)
31.8"
(808mm)
8.9"
(226mm)
1.4"
(36mm)
34.3"
(871mm)
28.3"
(719mm)
Bracket
Centers
28.3"
(719mm)
9.2"
(235mm)
0.8"
(21mm)
Vent Screen
Front and Back
Vent Screen
Display
Dimension
Y; See Pg. 2
See Pg. 2
Dimension
X
Dimension
Z
Center of
Gravity
Center of
Gravity
31.5" (800mm)
without Side Panels
Power
Cable Entry
21.26 x 7.87"
(540 x 200mm)
Power
Cable Entry
21.26 x 7.87"
(540 x 200mm)
TOP VIEW
BOTTOM VIEW
OVERALL
FRONT VIEW
LEFT SIDE VIEW
Front
Front
See Detail A
RIGHT SIDE VIEW
See
Page 2
8. All wiring is to be in accordance with national and local
electrical codes.
9. See page 2 of 5 drawing: UAM02010B for weight table
and centers of gravity for UPS at 208V.
10. See page 3 of 5 drawing: UAM02010C for weight table
and centers of gravity for UPS at 480V.
11. See page 4 of 5 drawing:UAM02010D for weight table and
centers of gravity for UPS at 600V.
12. See page 5 of 5 drawing:UAM02010E for weight table and
centers of gravity for UPS with internal maintenance bypass.
Refer to Tables 11 and 13 for Dimensions X, Y and Z in each Liebert APM model.