Installation Drawings
73
Liebert
®
APM
™
Figure 56 Battery cabinet outline drawing, weights and center of gravity 900mm cabinet
1. All dimensions are in inches (mm).
2. 24" (610) minimum clearance above
unit; 36" (914) front access required
for service.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through
removable access plates.
Remove, punch to suit conduit size and replace.
5. Control wiring and power wiring must be run in
separate conduits.
6. Only copper cables are recommended.
7. All wiring is to be in accordance with national
and local electrical codes.
UAM05012
Rev. 1
Cable Entry Area
8.2" x 8.7"
(210 x 220mm)
2 Places
Cable Entry Area
14.6" x 7.6"
(370 x 190mm)
Cable Entry Area
7.9" x 23.6"
(200 x 600mm)
7.5" (190mm)
Outside Frame
12.6" (320mm)
Outside Frame
5.5"
(140mm)
4" (101mm)
Outside Panel
17.1" (434mm)
Outside Panel
14.1"
(359mm)
Bracket Centers
14.1"
(359mm)
Bracket
Centers
35.8" (908mm)
20"
(507mm)
78.8"
(2000mm)
39.5" (1003mm)
Door Closed
18.2"
(464mm)
34.3"
(782mm)
35.2" (895mm)
FRONT VIEW
Without Covers
RIGHT SIDE VIEW
Center
of Gravity
Center
of Gravity
BOTTOM VIEW
FRONT
TOP VIEW
Maximum Door Swing - 120°
Z
Battery
and
Tray
X
Leveling
Feet
Center of Gravity, In. (mm)
Battery Type
12HX400-FR
12HX505-FR
12HX540-FR
X
17.3 (440)
17.3 (440)
17.3 (440)
Y
35 (890)
33 (840)
33 (840)
Z
20 (510)
20.9 (530)
20.9 (530)
Battery Type
12HX400-FR
12HX505-FR
12HX540-FR
Weight, Lb. (kg)
2693 (1224)
3245 (1475
3345 (1520)
Approximate Weights *
* For shipping weights, add 100 lb. (45 kg)