Instruction Manual
D103460X012
D3 Valve with easy-Drive Actuator
October 2017
15
ii. If positioning control is desired, contact your
or Local Business Partner to upgrade your
actuator to positioning control.
4. Diagnostics show a Motor Stall Fault.
a. The easyDrive electric actuator is designed to operate in a manner consistent with a pneumatic actuator. This
means that if the valve plug can not move to its commanded position, the actuator will stop, without damage,
and issue a Motor Stall Fault warning. When the command signal changes outside of the deadband (Modbus
register 40036), it will attempt to move again. Recalibrate the actuator span per instructions in the Startup
section of this manual.
5. Position on D3 is not accurate (proportional positioning units only).
a. If the position of a D3 is too high (i.e. 50% is much higher than 50% on the bonnet), check the valve type. If valve
type is D4, change to D3, cycle power, and recalibrate.
b. If the local analog input is being used (420mA or 15V), the analog inputs of the actuator may be calibrated to
match the input signal.
i. Command 0% (4mA or 1V).
ii. Using a Modbus link, send a 1 to register 40004 or use the Fisher easyDrive configuration software by clicking
the button “Analog Cal at 0%”.
iii. Command 100% (20mA or 5V).
iv. Using a Modbus link, send a 1 to register 40005 or use the Fisher easyDrive configuration software by clicking
the button “Analog Cal at 100%”.
Figure 9. Adjusts to Vary Flow Capacity (Shown with Valve Plug in Seated Position)
CLOSED
50%
100%
CLOSED
50%
100%
USE 5/32 INCH
ALLEN KEY
FULL CAPACITY SETTING (FACTORY SET)
15 mm (0.6 INCH) TRAVEL
NOTE: USE THE WIDELY-SPACED TRAVEL INDICATORS,
AS SHOWN ON THE LEFT PORTION OF THIS VIEW.
REDUCED CAPACITY SETTING
10 mm (0.4 INCH) TRAVEL
NOTE: USE THE CLOSELY-SPACED TRAVEL INDICATORS,
AS SHOWN ON THE RIGHT PORTION OF THIS VIEW.
STEM CONNECTOR
INDICATES TRAVEL
STEM CONNECTOR
INDICATES TRAVEL
Setting the Valve Flow Adjuster
The flow setting may only be adjusted if the 0.375 and 0.75 inch port sizes are installed and only when using the on/off
version.