Instruction Manual
D103460X012
D3 Valve with easy-Drive Actuator
October 2017
9
This order of operation must always be maintained when powering the unit on if no external 250 ohm resistor is used:
1. 12/24VDC power on
2. 420mA control signal engaged
This order of operation must always be maintained when powering the unit off:
1. 420mA control signal disengaged
2. 12/24VDC power off
The result of not following this order of operation could result in permanent damage to the analog input circuitry. This
damage can result in the inability of the controller to see the control signal, resulting in the actuator moving the valve
plug to the loss of signal position.
Default Input Signals
The D3 with easyDrive comes from the factory calibrated and ready for use with the following default input signals
shown in table 2.
Table 2. D3 easy-Drive Default Input Signals
CONFIGURATION
ON/OFF
POSITIONING
Input Signal
L2e (dual dry contact)
4-20 mA
Configuration
Input Configuration
There are 2 functional configurations available for the easyDrive electric actuator: On/Off and Positioning. It is not
possible to change an actuator from On/Off to Positioning after it has been delivered from the factory. Version 4.21
and higher firmware will allow a positioning unit to be changed to on/off.
All available input signals are shown in table 3.
Table 3. All Available Input Signals
CONFIGURATION
ON/OFF
POSITIONING
Control Source
Modbus
Local
Modbus
Local
Input Signal
Modbus
L2e Dual Dry
Contact (default)
Single Dry Contact
Modbus
4-20 mA (default)
1-5 V
If you are using the default inputs signals, and the valve has not been disassembled or adjusted in any way, there is no
need to recalibrate the assembly. You can proceed directly to Startup (page 12).
Changing the Inputs from Default Settings
All configuration within the valve is done by setting values in Modbus registers. This can be done using any Modbus
master (flow computer, PLC, PC). Configuration software, providing a visual interface to the registers, is available
through your
or Local Business Partner.
Modbus setup
Use the instructions in the instruction manual for the Modbus master to initiate the connection. The D3 with
easyDrive electric actuator Modbus factory defaults are Address 1, 9600 baud, even parity, 1 stop bit.