Communications
The flow computer includes three serial communication ports. The serial ports allow
communication using DNP3, Modbus, BSAP, and ROC protocols.
Table 1-3: Serial Ports
Port
Type
Use
COM1
Serial communications
Software-selectable for RS-232, RS-
485 (2-wire), RS-485/422 (4-wire)
operation
4-wire
RS-232, RS-485 (2-wire), RS-485/422 (4-wire)
communication to host or other devices. 4-
wire used with external radio.
COM2
Serial communications
Software-selectable for RS-232, or
RS-485 (2-wire) operation
2-wire
RS-232 or RS-485 (2-wire) communication to
host or other devices.
COM3
Serial communications
Software-selectable for RS-232, or
RS-485 (2-wire) operation
2-wire
RS-232 or RS-485 (2-wire) communication to
host or other devices.
Human-Machine Interface (HMI) Module
The flow computer includes an HMI module with an optional liquid crystal display (LCD) for local
operator access to the device. The LCD, if present, shows a series of menus that sequentially display
the current values of particular process variables. A configuration parameter in FBxConnect
determines whether you must log in first to view the menus. If required, you log in by selecting
alphanumeric characters by scrolling through a list until you select the correct character.
The HMI module includes four LEDs to provide status information. Units with the display include
four infrared (IR) buttons for operator interaction.
To conserve power, the HMI module enters sleep mode after a period of inactivity. Sleep mode
disables FBxWifi communication. In FBxConnect, you can configure the number of minutes of
inactivity triggering sleep mode through the LCD Sleep Time parameter. Setting this parameter to
0 disables sleep mode which keeps the HMI module on but uses significantly more power.
Summary of Contents for FB1100
Page 14: ...Emerson FB1100 Flow Computer Instruction Manual D301752X012 August 2020 10 Introduction ...
Page 48: ...Emerson FB1100 Flow Computer Instruction Manual D301752X012 August 2020 44 Installation ...
Page 87: ...Emerson FB1100 Flow Computer Instruction Manual D301752X012 August 2020 Index 83 ...