1592038420 XRB30-60-70-77CH EN v1.1 2021.09.15
XRB
28/38
LiG EMt
LiG,
ALL
With
LCi=0
:
-
Digital input 1 activates light out. Any OFF command from button, serial
command or energy saving will take effect.
-
If
n01>0
and
t01>0
, digital input 2 can switch OFF light out when
t01
ends.
With
LCi>0
:
-
Digital input 1 activates light out until
LCi
ends. Any OFF command from button,
serial command or energy saving will take effect.
-
If
n01>0
and
t01>0
, timers
LCi
and
t01
can overlap. If one of them is active, the
activation of the other one will be able to prolong the light out ON status.
LiG
ES
n.a.
Digital input 1 change light output. If
LCi=0
, light output will be activated and
deactivated with digital input. Il
LCi>0
, light output will be activated with digital input
and forced OFF when
LCi
ends.
Digital input 2 can change light output status if
LdE=Y
.
ES
dor
n.a.
Digital input 1 will change light output only if
LdE=Y
.
Digital input 2 can change light output, only if
CLY=Y
, and in the following ways:
-
If
LCi=0
then light output will be switched ON and OFF following the digital
input 2 status
-
If
LCi>0
then light output will be switched ON following the digital input 2
status and switched OFF when
LCi
ends.
ES
LiG
n.a.
Digital input 1 will change light output only if
LdE=Y
.
Digital input 2 can change light output in the following ways:
-
If
LCi=0
then light output will be switched ON and OFF following the digital
input 2 status
-
If
LCi>0
then light output will be switched ON following the digital input 2
status and switched OFF when
LCi
ends.
ES
EMt
ES
Digital input 1 will change lights only if
LdE=Y
.
Digital input 2 will be inhibited.
ES
EMt
LiG
Digital input 1 will change light status only if
LdE=Y
.
Digital input 2 can change light status only if
t01>0
and
n01>0
.
If time
t01
is running, a light OFF command from digital input 1 will take effect only
when
t01
ends.
If light is OFF due to digital input 1, after
n01
motion detections the light will be
switched ON for
t01
(temporary activation in energy saving).
If digital input 2 activates light (par.
t01>0
and
n01>0
), a subsequent digital input 1
command will change light status when
LdE=Y
.
ES
EMt ALL
Digital input 1 will change light status only if
LdE=Y
.
Digital input 2 can change light status only if
t01>0
and
n01>0
.
If time
t01
is running, a light OFF command from digital input 1 will take effect only
when
t01
ends.
If light is OFF due to digital input 1, after
n01
motion detections the light will be
switched ON for
t01
(temporary activation in energy saving).
If digital input 2 activates light (par.
t01>0
and
n01>0
), a subsequent digital input 1
command will change light status when
LdE=Y
.
Digital input 2 does not change ES status (the energy saving functions are inhibited,
par.
nES
is not take into consideration).
15.
INTERNAL COUNTERS
The next table shows the available counters.
n1H
Number of activations for relay output oA1 (thousands of)
n1L
Number of activations for relay output oA1 (units of)
n2H
Number of activations for relay output oA2 (thousands of)
n2L
Number of activations for relay output oA2 (units of)
n3H
Number of activations for relay output oA3 (thousands of)
n3L
Number of activations for relay output oA3 (units of)