1592038420 XRB30-60-70-77CH EN v1.1 2021.09.15
XRB
20/38
Label Description
LT
NT
Level
Ld6
6th defrost starting time
00:00 00:00
Pr2
Adr
Serial address
1
1
Pr1
bAU
Baudrate
96
96
Pr1
OnC
ONOFF button configuration (right lower side)
nu
nu
Pr2
On2
ONOFF button timed (3sec) configuration (right lower side)
OFF
OFF
Pr2
LGC
Light button configuration (left upper side)
LiG
LiG
Pr2
LG2
Light button timed (3sec) configuration (left upper side)
LiG
LiG
Pr2
ESC
Energy saving button configuration (left middle side)
nu
nu
Pr2
ES2
Energy saving button timed (3sec) configuration (left middle side)
ES
ES
Pr2
dnC
Down button configuration
nu
nu
Pr2
dn2
Down button timed (3sec) configuration
Lnt
Lnt
Pr2
dP1
Probe P1 value visualization
r.o.
r.o.
Pr1
dP2
Probe P2 value visualization
r.o.
r.o.
Pr1
dP3
Probe P3 value visualization
r.o.
r.o.
Pr1
dP4
Probe P4 value visualization
r.o.
r.o.
Pr1
rSE
Real regulation Set Point (SET + HES + SETd)
r.o.
r.o.
Pr1
FdY
Firmware release date: day
r.o.
r.o.
Pr1
FMn
Firmware release date: month
r.o.
r.o.
Pr1
FYr
Firmware release date: year
r.o.
r.o.
Pr1
rEL
Firmware release
r.o.
r.o.
Pr1
Ptb
Parameter map version
r.o.
r.o.
Pr1
NOTES:
-
“r.o.” stands for read only values
-
Default factory settings here indicated are valid for XRB77CH and XRB70CH only
-
Some parameters could not be present in other versions (for example XRB30CH) due to platform
specific limitations
-
RTC parameters are present only in models equipped with RTC option.
9.
REGULATION
The regulation is based on the temperature measured
by the thermostat probe (P1) with a positive differential
compared to the set point: if the temperature increases
and reaches the set point plus differential, the
compressor will start. The compressor will stop when
the temperature reaches the set point value again. In
case of fault because of the thermostat probe, the start
and stop of the compressor are timed through
parameters
CoF
and
Con
.
10.
ENERGY SAVING ALGORITHMS
The device permits to set different temperature to be used during normal and reduced power use. The
standard SET-POINT (
SET
) is used to maintain the temperature at a certain value when the energy saving
status (ES) is not active. On the other side, when the ES status is active a different SET-POINT (
SET_ES
),
higher than the standard one, will be used. The parameter
HES
will have to be set to change the regulation
temperature according to the following formula:
SET_ES = SET + HES
There are also two different differential values for SET and SET_ES, which are used for compressor cut-in
and cut-out: when ES status is active the
HYE
parameter will be used instead of the
HY
parameter.