1592038420 XRB30-60-70-77CH EN v1.1 2021.09.15
XRB
15/38
7.1.12 REAL TIME CLOCK
Hur
Hours:
0 to 23 hours
Min
Minutes:
0 to 59 minutes
dAY
Day of the week:
Sun to Sat
dYM
Day of the month:
1 to 31
Mon
Month:
1 to 12
YAr
Year:
00 to 99
Hd1
First day of weekend:
(Sun to SAt; nu) set the first day of the weekend.
Hd2
Second day of weekend:
(Sun to SAt; nu) set the second day of the weekend.
iLE
Energy saving cycle start time on working days:
(00h00min to 23h50min) set the activation
time of the Energy Saving cycle on working days.
dLE
Energy saving cycle duration on working days:
(00h00min to 24h00min) set the duration of
the Energy Saving cycle on working days. NOTE: see the ES paragraph to more information
about interaction with RTC and energy saving mode.
iSE
Energy saving cycle start time on weekends:
(00h00min to 23h50min) set the activation time
of the Energy Saving during the weekend.
dSE
Energy saving cycle duration on weekends:
(00h00min to 24h00min) set the duration of the
Energy Saving cycle during the weekend.
ddx
Daily defrost enabled:
(n; Y) to enable the
Ld1 to Ld6
defrost operations for any day of the
week.
•
dd1
= Sunday defrost
•
dd2
= Monday defrost
•
dd3
= Tuesday defrost
•
dd4
= Wednesday defrost
•
dd5
= Thursday defrost
•
dd6
= Friday defrost
•
dd7
= Saturday defrost
Ldx
Defrost start time:
(00h00min to 23h50min) these parameters set the beginning of the
programmable defrost cycles during any
ddx
day. Example: when
Ld2=12.4,
the second defrost
starts at 12:40 am during working days.
7.1.13 SERIAL COMMUNICATION
Adr
Serial address:
(1 to 247) device address for Modbus communication.
bAU
Baudrate:
(9.6; 19.2) 9.6=9600baud; 19.2=19200baud. Select the correct baudrate for serial
communication.
7.1.14 USER INTERFACE
onC
OFF button configuration (right lower side): nu
=not used;
oFF
=ON/OFF function;
ES
=energy
saving mode activation and deactivation.
on2
OFF button timed (3sec) configuration (right lower side): nu
=not used;
oFF
=ON/OFF
function;
ES
= energy saving mode activation and deactivation.
LGC
Light button configuration (left upper side): nu
=not used;
Lig
=light output;
AUS
=auxiliary
output;
Lnt
=change configuration
LG2
Light button timed (3sec) configuration (left upper side): nu
=not used;
ErA
=reset energy
saving pattern;
Lnt
=change configuration.
ESC
AUS or ES button configuration (left middle side): nu
=not used;
Pb2
=Probe Pb2 visualization;
AUS
=auxiliary output;
ES
=energy saving mode activation and deactivation.
ES2
DEFROST or ES button timed (3sec) configuration (left middle side): nu
=not used;
dEF
=defrost activation;
AUS
=auxiliary output;
ES
=energy saving mode activation and
deactivation
dnC
DOWN button configuration: nu
=not used;
Std
=standard functions;
Lnt
=change configuration.
dn2
DOWN button configuration: nu
=not used;
Std
=standard functions;
Lnt
=change configuration;
Pdn
=Pull Down activation.
7.1.15 INFORMATION (READ ONLY)
d1
Probe P1 value visualization
d2
Probe P2 value visualization
d3
Probe P3 value visualization
d4
Probe P4 value visualization