1592038420 XRB30-60-70-77CH EN v1.1 2021.09.15
XRB
16/38
rSE
Real regulation Set Point
FdY
Firmware release date: day
FMt
Firmware release date: month
FYr
Firmware release date: year
rEL
Firmware Release
Ptb
Parameter code table
8.
PARAMETER CONFIGURATION
Label Description
LT
NT
Level
rtC
Real time clock menu
0
0
Pr1
SET
Setpoint
3.0
36
LS
Minimum Set point
-50.0
-58
Pr1
US
Maximum Set point
50.0
122
Pr1
Hy
Compressor regulation differential in normal mode
3.0
6
Pr1
HyE
Compressor regulation differential in energy saving mode
3.0
6
Pr1
Hyd
Deadband output regulation (oAx=db) differential
3.0
6
Pr2
rAr
Delay between compressor and db output (oAx=db) activation and vice
versa
0
0
Pr2
odS
Output activation delay at start-up
1
1
Pr1
AC
Anti-short cycle delay
1
1
Pr1
AC1
Anti-short cycle delay (2nd compressor)
15
15
Pr2
rtr
Regulation percentage=F(P1; P2) (100=P1; 0=P2)
100
100
Pr1
oHt
Threshold for automatic activation of Pull Down in normal mode
(SET+HY+oHt)
10.0
20
Pr1
SCo
Differential during Pull Down (SEt-SCo)
1.0
2
Pr1
tSC
Maximum duration for Pull Down
00:30 00:30
Pr1
oHE
Threshold for automatic activation of Pull Down in energy saving mode
(SET+HES+HYE+oHE)
0.0
0
Pr1
SCE
Pull Down phase differential in energy saving (SEt+HYE-SCE)
0.0
0
Pr1
Con
Compressor ON time with faulty probe
5
5
Pr1
CoF
Compressor OFF time with faulty probe
10
10
Pr1
PbC
Probe selection
ntC
ntC
Pr2
ot
Probe P1 calibration
0.0
0
Pr2
P2P
Probe P2 presence
yes
yes
Pr2
o2
Probe P2 calibration
0.0
0
Pr2
P3P
Probe P3 presence
no
no
Pr2
o3
Probe P3 calibration
0.0
0
Pr2
P4P
Probe P4 presence
no
no
Pr2
o4
Probe P4 calibration
0.0
0
Pr2
iCO
Icon visualization
yes
yes
Pr2
CF
Temperature measurement unit: Celsius; Fahrenheit
°C
°F
Pr2
rES
Temperature resolution: decimal, integer
dE
dE
Pr2
Lod
Probe default displayed
P1
P1
Pr1
dLy
Temperature display delay (resolution 10 sec)
00:00 00:00
Pr2
dtr
Probe visualization percentage=F(P1;P2) (ex: dtr=1 means
VALUE=0.01*P1+0.99*P2)
99
99
Pr2
EdF
Defrost mode
in
in
Pr2
tdF
Defrost type: electric heating, hot gas
EL
EL
Pr1
dFP
Probe selection for defrost control
P2
P2
Pr1
dtE
End defrost temperature
10.0
50
Pr1