4.3 LOCK THE KEYBOARD
Keep both
UP
and
DOWN
buttons pressed for more than 3 sec.
The “
oFF
” label will be displayed and the keyboard will be locked. If any button is pressed more than 3 sec,
the “
oFF
” message will be displayed.
4.4 UNLOCK THE KEYBOARD
Keep both
UP
and
DOWN
buttons pressed together for more than 3 sec till the
“on”
message will be
displayed.
4.5 PROGRAMMING MENU
To change the values of the parameters, operate as follows:
Enter the Programming mode by pressing the
SET+DOWN
buttons for 3 sec (“
°C
”
LED starts blinking).
Select the parameter to modify. Press the
SET
button to display the current value.
Use
UP
or
DOWN
buttons to change the current value.
Press
SET
to store the new value and move to the following parameter.
To exit:
Press
SET+UP
buttons or waits for 15 sec without pressing any key.
NOTE:
the set value is stored even when the procedure exits by time-out.
4.5.1 ENTER THE MENU PR2
Enter the Programming mode by pressing
SET+DOWN
buttons for 3 sec (“
°C
”
or “
°F
” LED starts blinking).
COMPRESSOR
OFF
Compressor output OFF
FLASH
Anti short cycle delay is running
ON
Compressor output ON
FAN
OFF
Evaporator fan output OFF
FLASH
Activation delay is running
ON
Evaporator fan output ON
DEFROST
OFF
Defrost OFF
FLASH
Activation delay or drain time is running
ON
Defrost ON
AUX
OFF
Auxiliary output OFF or not available
FLASH
Not used
ON
Auxiliary output ON
ENERGY SAVING
OFF
Energy saving OFF
FLASH
Not used
ON
Energy saving ON
PULL DOWN
OFF
Pull Down OFF
FLASH
Not used
ON
Pull down ON
ALARM
OFF
No alarm is active
FLASH
Not used
ON
Some alarm is active
Celsius Degree
OFF
Not used
FLASH
Not used
ON
Measurement units: Celsius degree
Fahrenheit Degree
OFF
Not used
FLASH
Not used
ON
Measurement units: Fahrenheit degree