1592038420 XRB30-60-70-77CH EN v1.1 2021.09.15
XRB
17/38
Label Description
LT
NT
Level
idF
Interval between two successive defrost cycles
8
8
Pr1
MdF
Maximum length of defrost cycle
20
20
Pr1
dSd
Start defrost delay
0
0
Pr1
dFd
Displaying during defrost
dEF
dEF
Pr1
dAd
Temperature display delay after any defrost cycle
0
0
Pr1
Fdt
Draining time
2
2
Pr1
dPo
Defrost cycle enebled at stat-up
no
no
Pr1
dAP
Defrost delay after Pull Down
0
0
Pr1
od1
Automatic defrost (at the beginning of any energy saving)
no
no
Pr2
od3
Optimized defrost
nu
nu
Pr2
Syd
Tipe of synchronized defrost
nu
nu
Pr2
dt1
Differential temperature for latent heating control
0.3
1
Pr2
dt2
Delta=Troom-Tevap (used if od3=Y)
0.5
1
Pr2
FAP
Probe selection for evaporator fan
nP
nP
Pr1
FSt
Evaporator fan stop temperature
16.0
60
Pr1
HYF
Evaporator fan regulator differential
2.0
20
Pr1
OF2
Evaporator fan offset in energy saving
0.1
1
Pr1
FnC
Evaporator fan operating mode
C_n
C_n
Pr1
Fnd
Evaporator fan delay after defrost cycle
2
2
Pr1
FCt
Differential temperature for cyclic activation of evaporator fans
(0=disabled)
0
0
Pr1
Fon
Evaporator fan ON time in normal mode (with compressor OFF)
1
1
Pr1
FoF
Evaporator fan OFF time in normal mode (with compressor OFF)
1
1
Pr1
Ft
Evaporator fan controlled during defrost
no
no
Pr1
Fo1
Evaporator fan ON time in energy saving (with compressor OFF)
1
1
Pr1
FF1
Evaporator fan OFF time in energy saving (with compressor OFF)
2
2
Pr1
ACH
Type of control for auxiliary regulator
CL
CL
Pr2
SAA
Set point for auxiliary regulator
12.0
60
Pr2
SHy
Auxiliary regulator differential
1.0
1
Pr2
ArP
Probe selection for auxiliary regulator
nP
nP
Pr2
Sdd
Auxiliary regulator disabled during any defrost cycle
no
no
Pr2
btA
Base time for parameters Ato and AtF
sec
sec
Pr2
Ato
Interval of time with auxiliary output ON
0
0
Pr2
Atf
Interval of time with auxiliary output OFF
0
0
Pr2
ALP
Probe selection for temperature alarms
P1
P1
Pr1
ALC
Temperature alarms configuration: relative, absolute
Ab
Ab
Pr1
ALL
Low temperature alarm
-20.0
-4
Pr1
ALU
High temperature alarm
20.0
68
Pr1
AFH
Temperature alarm differential
2.0
4
Pr1
ALd
Temperature alarm delay
1
1
Pr1
dot
Temperature alarm delay with open door
00:10 00:10
Pr1
dAo
Temperature alarm delay at start-up
01:00 01:00
Pr1
AP2
Probe selection for 2nd temperature alarm
nP
nP
Pr2
AU1
Pre-alarm threshold for 2nd temperature alarm (absolute value)
0.0
0
Pr2
AH1
2nd high temperature pre-alarm differential
2.0
4
Pr2
Ad1
2nd high temperature pre-alarm delay
0
0
Pr2
AL2
2nd low temperature alarm
-10.0
-67
Pr2