1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx
iProCHILL
200/205
ACF17
one or more pressure probes defined on a XEV20D module which is not
configured by parameters Et09
– Et16
when SP01 <=1 and
Et02≠3 or when SP01>=2 and Et02≠4, configured
XEV20D probes as pressure type.
ACF18
If stepless compressor is enabled (SL01
≠0):
SL06>=SL07*10
ST11
≠ 2 (2=neutral zone regulation)
In one circuit, more than one compressor is configured (CF05
…CF08>
1)
compressor is configured but relevant relay Compressor 1…4
intermittent valve is not configured (DO type=52…55).
ACF19
Probe selected by Un05 is not configured.
Probe selected by Un10 is not configured.
Display in keyboard
Conf AL1
…Conf AL19
Cause of activation
Incorrect programming
Reset
Correct programming
Reset
Automatic
Icon
flashing
Action
Alarm relay (DO type=1) + buzzer activated
Regulators
Alarm
Relay + buzzer activated
Other loads
Off
10.43 FUNCTION NOT AVAILABLE ALARM
Alarm code
AfnA
(Function not available alarm)
Display in keyboard
Func.not available
Cause of activation
Incorrect parameter configuration, enabled some function that not available
yet.
Set ST11 >2
Set DP05-DP08 value >0
Set SP02 =6
Set SP12=1
Set CO19-CO34 value >0
If CO12=2 (Star-delta start-up), relay Star-delta relay is no configured
on board, they are configured in expansion IO board.
If SL01
≠
0(stepless compressor enabled)
o
CO09=1/3.
o
No relays configured as
Compressor 1…4 Unloader 1(DO
type=79,87,95,103)
o
Relays (S
crew) Compressor 1…4 intermittent valve (DO
type=52-55) are not configured on board, they are configured in
expansion IO board.
o
Relays
Compressor 1…4 Unloader 2(DO type=80,88,96,104)
are not configured on board, they are configured in expansion IO
board.
Reset
Correct programming
Reset
Automatic
Icon
flashing