iProCHILL
157/205
9.
ANALOGUE - DIGITAL INPUTS/OUTPUTS CONFIGURATIONS
On board of the controller, it allows to configure 20 DI, 15 DO, 10 AI and 6 AO in maximum. If more I/O
needed, please use expansion module IPROEX60D. For one IPROEX60D, it can connect with 3 DI, 6 DO, 7
AI and 3 AO. It can has 4 IPROEX60D at most. In addition, 4 electronic thermostatic drivers XEV20D can
provide 16 more AI (4 for each).
Use parameters in group IO to configure analogue-digital inputs/outputs.
DIGITAL INPUTS CONFIGURATION
IO11
– IO30:
On board DI (1 - 20)
IO75
– IO77:
1
st
expansion DI (1 - 3)
IO94
– IO96:
2
nd
expansion DI (1 - 3)
IO113
– IO115: 3
rd
expansion DI (1 - 3)
IO132
– IO134: 4
th
expansion DI (1 - 3)
DIGITAL OUTPUTS CONFIGURATION
IO31
– IO45:
On board relays (1 - 15)
IO78
– IO83:
1
st
expansion relays (1 - 6)
IO97
– IO102:
2
nd
expansion relays (1 - 6)
IO116
– IO121: 3
rd
expansion relays (1 - 6)
IO135
– IO140: 4
th
expansion relays (1 - 6)
ANALOGUE INPUTS CONFIGURATION
IO01
– IO10:
On board probes (1 - 10)
IO52
– IO55:
1
st
XEV20D probes (1 - 4)
IO56
– IO59:
2
nd
XEV20D probes (1 - 4)
IO60
– IO63:
3
rd
XEV20D probes (1 - 4)
IO64
– IO67:
4
th
XEV20D probes (1 - 4)
IO68
– IO74:
1
st
expansion probes (1 - 7)
IO87
– IO93:
2
nd
expansion probes (1 - 7)
IO106
– IO112: 3
rd
expansion probes (1 - 7)
IO125
– IO131: 4
th
expansion probes (1 - 7)
ANALOGUE OUTPUTS CONFIGURATION
IO46
– IO51:
On board AO (1 - 6)
IO84
– IO86:
1
st
expansion AO (1 - 3)
IO103
– IO105: 2
nd
expansion AO (1 - 3)
IO122
– IO124: 3
rd
expansion AO (1 - 3)
IO141
– IO143: 4
th
expansion AO (1 - 3)
Note:
For digital inputs/outputs, it is possible to select polarity. In I/O configuration, use prefix
“o” to indicate “open”
polarity which means the DI/DO is activated when contact is open; use prefix
“c” to indicate “close” polarity
which means the DI/DO is activated when contact is closed.
For example:
IO11 = o1 - Remote ON/OFF
IO11 = c1 - Remote ON/OFF
They all mean DI01 is configured as
“Remote ON/OFF” but with different polarity. And the DI type is 1.
In the paragraphs below, we will use
“
DI type
”, “
DO type
”, “
AI type
” and “
AO type
” to indicated function
index of all the I/O.
For analogue inputs/outputs, it is also possible to configured as digital inputs/outputs. For example an AI can
assume values from 0 to 66 (if configured as analog) and from 67 (that correspond to o1) to 296 (that
correspond to c115).
Remember that:
AO1, AO2, AO3 and AO4 can be configured only as 0-10V;
AO5 and AO6 can be configured as 0-10V, PWM and 4-20mA;
in the expansions modules, the AO can be configured only as 0-10V.