1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx
iProCHILL
165/205
9.4
CONFIGURATION OF THE OUT1 / OUT4 PROPORTIONAL OUTPUTS (AO TYPE)
0÷10V output signal
0.
Output disabled
1.
0÷10V proportional output for circuit n° 1 fan speed control
2.
0÷10V proportional output for circuit n° 2 fan speed control
3.
0÷10V proportional output for circuit n° 3 fan speed control
4.
0÷10V proportional output for circuit n° 4 fan speed control
5.
0÷10V dampers control proportional output / free-cooling mixer valve
6.
0÷10V hot water three-way valve control 0÷10V proportional output
7.
0÷10V auxiliary output n° 1
8.
0÷10V auxiliary output n° 2
9.
0÷10V auxiliary output n° 3
10. 0÷10V auxiliary output n° 4
11. Circuit n° 1 compressor 1 0÷10V modulating output
12. Circuit n° 2 compressor 1 0÷10V modulating output
13. Circuit n° 3 compressor 1 0÷10V modulating output
14. Circuit n° 4 compressor 1 0÷10V modulating output
15. Modulating output 0÷10V auxiliary heating
External relay driving ON/OFF output (o1-c195, see relevant configurations)
9.5
CONFIGURATION OF THE OUT5 / OUT6 PROPORTIONAL OUTPUTS
4÷20mA - 0÷10V - PWM configurable output signal
From 0 to 14 as Out1-Out4 configuration
16. Circuit N° 1 external phase-cut command PWM signal = TF 1
17. Circuit N° 2 external phase-cut command PWM signal = TF 2
18. 4÷20mA proportional output for circuit n° 1 fan speed control
19. 4÷20mA proportional output for circuit n° 2 fan speed control
20. 4÷20mA proportional output for circuit n° 3 fan speed control
21. 4÷20mA proportional output for circuit n° 4 fan speed control
22. 4÷20mA dampers control proportional output / free-cooling mixer valve
23. 4÷20mA hot water three-way valve control proportional output
24. 4÷20mA auxiliary output n° 1
25. 4÷20mA auxiliary output n° 2
26. 4÷20mA auxiliary output n° 3
27. 4÷20mA auxiliary output n° 4
28. Circuit n° 1 compressor 1 4÷20mA modulating output
29. Circuit n° 2 compressor 1 4÷20mA modulating output
30. Circuit n° 3 compressor 1 4÷20mA modulating output
31. Circuit n° 4 compressor 1 4÷20mA modulating output
32. Modulating output 4÷20mA auxiliary heating
External relay driving ON/OFF output (o1-c195, see relevant configurations)
9.6
ANALOGUE INPUTS CALIBRATION
In case of analogue input value is not very precise, you can use parameters in group CA to set a offset to
probe value to make the measurement more close to the actual value.
AI value used for controlling = AI measured value + calibration
CA01
– CA10:
On board probes calibration (1 - 10)
CA11
– CA14:
1
st
XEV20D probes calibration (1 - 4)
CA15
– CA18:
2
nd
XEV20D probes calibration (1 - 4)
CA19
– CA22:
3
rd
XEV20D probes calibration (1 - 4)
CA23
– CA26:
4
th
XEV20D probes calibration (1 - 4)
CA27
– CA33:
1
st
expansion probes calibration (1 - 7)
CA34
– CA40:
2
nd
expansion probes calibration (1 - 7)
CA41
– CA47:
3
rd
expansion probes calibration (1 - 7)
CA48
– CA54:
4
th
expansion probes calibration (1 - 7)