1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx
iProCHILL
132/205
FA6
Single or separate condensation fan
0= unique condensation (1 / 2 / 3 / 4)
1= separate condensers
2= unique by circuits (1
– 2) / (3 – 4)
0
2
FA7
Pre ventilation before switching compressor ON. It allows you to set a start up
time for the fans at the maximum speed in chiller mode before the
compressor is switched on, in order to prepare for the sudden increase in
condensation temperature / pressure (that starting up the compressor
entails) and improving regulation. (only if FA01 = 4)
0
250
Sec
Chiller mode
FA8
Minimum operation speed of the chiller fans. This allows
you to set a minimum value for proportional fan regulation in chiller
mode. It is expressed as a percentage of the maximum voltage
allowed.
0
FA16
%
FA9
Maximum operation speed of the chiller fans. This allows
you to set a maximum value for proportional fan regulation in chiller
mode. It is expressed as a percentage of the maximum voltage
allowed.
FA16
100
%
FA10
Proportional regulation
Minimum fan speed Set temperature/pressure in chiller mode. This allows
you to set the condensation temperature / pressure value in
chiller
that
corresponds to the minimum fan speed.
Step regulation
SET 1st STEP
This allows you to set the condensation temperature
/ pressure value in chiller mode that corresponds to operation in ON
of the relay output, configured as the 1st condensation fan speed
step.
-50.0
-58
0.0
0
110
230
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
FA11
Proportional regulation
Set maximum fan speed temperature/pressure in chiller mode. This
allows you to set the condensation temperature / pressure value in chiller
that corresponds to the maximum fan speed.
Step regulation
SET 2nd STEP
This allows you to set the condensation temperature /
pressure value in chiller mode that corresponds to the operation in
ON of the relay output, configured as the 2nd condensation fan speed
step.
-50.0
-58
0.0
0
110
230
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
FA12
Proportional regulation
Proportional band regulation of fans in chiller mode This allows you to set
a temperature / pressure differential that corresponds to a variation from
minimum to maximum fan speed.
Step regulation
With Par. FA01=2/3 becomes the differential on the step itself of circuit 1
in chiller (see fans regulation graph).
0.1
0
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
FA13
Proportional regulation
Differential CUT- OFF in chiller. This allows you to set a temperature /
pressure differential in chiller mode to shut off the fan.
Step regulation
With Par. FA01=2/3 becomes the differential on the step itself of circuit 2
in chiller (see fans regulation graph).
0.1
0
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
FA14
Over ride CUT- OFF in chiller. This allows you to set a temperature /
pressure differential in chiller mode, where the fan maintains minimum
speed.
0.1
0
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
FA15
CUT-OFF delay when fans are activated. This allows you to set a delay time
for the activation of the CUT - OFF function at fan start-up.
If at compressor start-up the proportional regulator requests the fans to be
shut off and FA15
≠
0, the fan will be forced at minimum speed for the set
time. If FA15=0, the function is not enabled.
0
250
Sec
FA16
Night function speed in chiller mode. This allows you to set a maximum
value for proportional regulation of the fans in chiller mode. It is
expressed as a percentage of the maximum voltage allowed.
FA8
FA9
%
Heat pump mode
FA17
Minimum fan speed in heat pump mode. This allows you to set a
minimum value for the proportional regulation of the fans in h.p. It is
expressed as a percentage of the maximum voltage allowed.
0
FA24
%
FA18
Maximum fan speed in heat pump mode. This allows you to set a
maximum value for the proportional regulation of the fans in h.p. It is
expressed as a percentage of the maximum voltage allowed.
FA24
100
%