1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx
iProCHILL
19/205
5.1.4 Change Over Function
SP10
Automatic chiller / heat pump mode changeover setting
-50.0
-58
110
230
°C
°F
Dec
int
SP11
Automatic chiller / heat pump mode changeover differential
0.1
1
25.0
45
°C
°F
Dec
int
The status change over can only take place if these necessary conditions are present at the same time,
otherwise the unit
REMAINS in stand - by:
1. CF02=3 (chiller with heat pump)
2. SP09=2 is an NTC probe configured as an
Dynamic/boiler function/change over set-point external
air temperature NTC temperature probe
(AI type=35)
3. the regulation probe selected must not be in error conditions
AUTOMATIC CHANGE OVER REGULATOR GRAPHICS
PBr
CHILLER
HEAT PUMP
SET SP10
Diff. SP11
Parameters that regulated the change over function
SP10
allows setting the change over set point. If the selection of the working mode from analogue input is
enabled, it represents the temperature value detected by the regulation probe below which the device
imposes the working in heating mode
SP11
allows setting the change over differential. If the selection of the working mode from analogue input is
enabled, it represents the temperature differential on the basis of which the device imposes the working in
cooling mode
For temperature of the external air included in the SP11 differential, it is allowed to change the working mode
from the keyboard.
NTC external air temperature regulation NTC probe > SP10+ SP11, the unit is switched-on in cooling mode.
NTC external air temperature regulation NTC probe < SP10, the unit is switched-on in heating mode.
5.2
UNIT SWITH ON/OFF BY RTC
5.2.1 Working With Clock Disabling Digital Input
ES 1
Start of working time band 1 (0-24)
0
24.00
Hr
10 Min
ES 2
End of working time band 1 (0-24)
0
24.00
Hr
10 Min
ES 3
Start of working time band 2 (0-24)
0
24.00
Hr
10 Min
ES 4
End of working time band 2 (0-24)
0
24.00
Hr
10 Min
ES 5
Start of working time band 3 (0-24)
0
24.00
Hr
10 Min
ES 6
End of working time band 3 (0-24)
0
24.00
Hr
10 Min
ES18
Monday automatic shutdown time band
0
7
ES19
Tuesday automatic shutdown time band
0
7
ES20
Wednesday automatic shutdown time band
0
7
ES21
Thursday automatic shutdown time band
0
7
ES22
Friday automatic shutdown time band
0
7
ES23
Saturday automatic shutdown time band
0
7
ES24
Sunday automatic shutdown time band
0
7
If the unit is switch off during switch-off time bands, the screen will be: