12 Chapter 2 Mechanical Installation
DataMate 3000 Series Air Conditioner User Manual
2.4.3 Installation Procedure
1. Secure the floorstand on the selected location. The outline and dimensions of the
floorstand are shown in Figure 2-6.
600
550
30 30 3 angle iron
or 25 25 2 square tube
Rubber cushion 8mm
Rubber cushion 8mm
hole for installing
expansive bolt M6 50
Sole
Steel plate 60 60 4
H>150
Figure 2-6 Floorstand
2. Lay a rubber cushion with 8~10mm thickness, as shown in Figure 2-6.
3. Uncrate the evaporator and place it onto the floorstand.
4. Rotate the grille to select the desired air discharge direction, as shown in Figure
2-7.
Grille can be rotated in
the arrow direction
Figure 2-7
Changing air discharge direction