54 Chapter 7 Troubleshooting
DataMate 3000 Series Air Conditioner User Manual
Symptom
Possible cause
Check or remedy
Equipment power voltage too low
Check for power voltage
No display, control
ler does not
respond. Equipment
has no output
Communication between control board
and interface board interrupted
Check connection between control board and
interface board
Room cooling load is small compared
with system capacity
Increase the temperature sensitivity setpoint
Short cycle alarm
Temperature sensitivity setpoint too
small
Increase the temperature sensitivity setpoint
Refrigerant leaked
Check for leaking place and recharge
Low pressure alarm
External environment temperature too
low
Contact Emerson
High temperature setpoint
unreasonable
Change the setpoint
High temperature
alarm
Room cooling load exceeds the
system capacity
Check for room seal or make capacity extension
Low temperature setpoint
unreasonable
Change the setpoint
Low temeperature
alarm
Heater operation current
unreasonable
Check the heater operation
Setpoint unreasonable
Change it
High humidity alarm
Vapor barrier is not done in the room
Check for the vapor barrier
Humidifier not used
Use optional humidifier
Humidifier needs to be serviced
Check the humidifier
Low humidity alarm
Setpoint unreasonable
Change it
Mains voltage abnormal
Check the input power
Power failure alarm
Power connection incorrect
Check the input power
Service alarm
A service interval is end
Service relative components and reset the alarm